Product guide
v4.5 - 12.18 .14 |
17
BACK TO T.O.C.
4 CONTACT & 4 VOLTAGE SENSOR - 4C4V
Add 4 non-isolated dry contact closure inputs and 4 non-isolated voltage
inputs to any Asentria base unit with an expansion slot.
• Voltage points: -60/+60 VDC
• Resolution: 0.1 VDC
• Accuracy: +/- 0.5 VDC
4 CONTACT & 4 ISOLATED VOLTAGE SENSOR - 4VI4C
Add 4 non-isolated dry contact closure inputs and 4 individually isolated voltage
inputs to any Asentria base unit with an expansion slot.
• Isolated voltage points: -60/+60 VDC
• Resolution: 0.1 VDC
• Accuracy: +/- 0.5 VDC
4 CONTACT & 4 LOW-CURRENT RELAY - 4C4R
Add 4 non-isolated dry contact inputs and 4 relay outputs to any Asentria base
unit with an expansion slot.
• Max switched VDC: 60
• Max switched power: 30W
• Max switched current: 0.6A
2 CONTACT & 4 LOW-CURRENT FORM C RELAYS (NO, NC) -
2C4RC
Add 2 non-isolated dry contact closure inputs and 4 Form C Relays to any
Asentria base unit.
• Mechanical relays retain state upon power cycle
• Mechanical relay current capacity: 0.6A
4 CONTACT, 1 WIEGAND INTERFACE W/POWER &
1 LOW-CURRENT RELAY - 4C1W1R
Add 4 non-isolated dry contact inputs, 1 Wiegand interface with power and 1 relay
output to any Asentria base unit with an expansion slot.
• Max switched VDC: 60
• Max switched power: 30W
• Max switched current: 0.6A
• For use with RFID Reader ESW-RFID1 and ESW-RFID2
EXPANSION SLOT 1EXPANSION SLOT 2EXPANSION SLOT 3EXPANSION SLOT 5
EXPANSION SLOT 4EXPANSION SLOT 6
Slot number arrangement (using the SiteBoss 550-6 as an example)
2 WIEGAND INTERFACE W/POWER & 2 LOW-
CURRENT RELAY - 2W2R
Add 2 Wiegand interface with power and 2 relay outputs to any Asentria
base unit with an expansion slot.
• Max switched VDC: 60
• Max switched power: 30W
• Max switched current: 0.6A
• For use with RFID Reader ESW-RFID1 and ESW-RFID2
4 VOLTAGE & (4) 4-20MA SENSOR - 4V4M
Add 4 non-isolated voltage inputs and 4 non-isolated 4-20mA current inputs to
any Asentria base unit with an expansion slot.
• Resolution: 0.1mA
• Accuracy: 0.1mA
4 CONTACT & (4) 4-20MA SENSOR - 4C4M
Add 4 non-isolated dry contact closure inputs and 4 non-isolated 4-20mA current
inputs to any Asentria base unit with an expansion slot.
• Resolution: 0.1mA
• Accuracy: 0.1mA
4 CONTACT & 4 ISOLATED 4-20MA SENSOR - 4MI4C
Add 4 non-isolated dry contact closure inputs and 4 individually isolated 4-20mA
current inputs to any Asentria base unit with an expansion slot.
• Resolution: 0.1mA
• Accuracy: 0.1mA
PART NUMBERS
Using the S550 catalog number as an example, the con guration order is listed
below. Note that the order in which Expansion cards are listed re ects the
Expansion Slot in which the card will be installed. Items with a * are truly optional
and are omitted if not desired.
BASE UNIT + MEMORY SIZE + *MODEM + *TEMP SENSOR +
POWER SUPPLY + *BATTERY BACKUP + *EXPANSION CARDS
Thus, the following are all valid part numbers:
• S550-6/32M/MD/T/ACUS-8V-8R-8C • S550-6/32M/ACEU-8C-4C4V
• S550-6/32M/ACUS-8V-8R-4S
Expansion Cards