0.3.en.06 UNRECOVERABLE condition—No blowers installed
NOTE: IMPORTANT
When this condition exists there will be two error messages.
The first message will be 0.3.en.05 and will identify the first blower.
The second message will be 0.3.en.06 and will identify the second blower.
The EMU cannot detect any installed blowers. Shutdown is imminent! The EMU will shut down the
enclosure in seven minutes unless you correct the problem. This condition report remains active
until you correct the problem or the EMU shuts down the power supplies, whichever occurs first.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Use the controller shutdown procedure to shut down the controllers.
3. Contact your authorized service representative.
CAUTION: An automatic shutdown and possible data corruption may result if the blower is
removed before a replacement is available.
Temperature conditions
The format of a temperature condition report is 0.4.en.ec, where:
• 0.4. is the temperature sensor element type
• en. is the two-character temperature sensor element
• ec is the error code
See Table 43 (page 128) to determine the location of each temperature sensor.
Table 43 Temperature sensor element numbering
Sensor locationSensorSensor locationSensor
Drive Bay 710.Power Supply 1 Exhaust01.
Drive Bay 811.Power Supply 2 Exhaust02.
Drive Bay 912.EMU03.
Drive Bay 1013.Drive Bay 104.
Drive Bay 1114.Drive Bay 205.
Drive Bay 1215.Drive Bay 306.
Drive Bay 1316.Drive Bay 407.
Drive Bay 1417.Drive Bay 508.
Drive Bay 609.
The following sections list the temperature condition reports and the default temperature thresholds.
Use HP Command View EVA to view the temperature sensor ranges for the disk drives, EMU, and
power supplies.
0.4.en.01 NONCRITICAL condition—High temperature
This condition report indicates that an element temperature is approaching, but has not reached,
the high temperature CRITICAL threshold. Continued operation under these conditions may result
in a CRITICAL condition. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Ensure that all elements are properly installed to maintain proper air flow.
128 EMU-generated condition reports