User manual
EMS SYSTEM 5000
USER MANUAL, ISSUE 2.4 – 19/11/09
7
6 Control Keyswitch:
The Control Keyswitch has three different positions. They are “OFF”, “ON” and
ISOLATED”.
Each of their functions are explained on the following page: -
6.1 OFF (Normal) Position Functionality: (Access Level 1)
With the control keyswitch in the “OFF” position,
the panel is at Access Level 1. The key is
removable in this position and it is recommended
that the panel is left in this position with the
key removed. The following control options are
available: -
Scroll Buttons
Operational when multiple events are
displayed to enable each event to be viewed.
Reset/Led
Test
Operates Status lamp test when system has
no events shown.
Silence Alarms
No operation.
Sound Alarms
No operation.
View Tests
2
nd
Feature
of key
Displays any device/zone currently in test.
This will automatically timeout and return to
the Front Screen if left in this mode.
View
Disablements
2
nd
Feature
of key
Displays any device/zone currently disabled.
This will automatically timeout and return to
the front screen if left in this mode.
View Faults
2
nd
Feature
of key
Displays any device currently in fault
condition. This will automatically timeout and
return to the front screen if left in this mode.
View Fires
2
nd
Feature
of key
Returns to view fire events if any of the other
view options used. This will automatically
timeout and return to the front screen if left
in this mode.
Status Lamps,
(see fig 2)
N/A Indicates the systems current status
System Menus N/A No Operation
OFF
position
ISOLATED
OFF
ON