User manual

EMS SYSTEM 5000
USER MANUAL, ISSUE 2.4 – 19/11/09
11
(A) Options:
FUNCTION DESCRIPTION
Passwords Contains 7 sub menus. This allows the option to change,
edit and delete PIN numbers if used.
Time and Date Gives the option to set and view the Time and Date.
Logging Enables you to view the entire log of events, (up to 1000
events), or to view the log at a certain date.
Fire System Options Allows access to (B) Fire System.
(B) Fire System:
FUNCTION DESCRIPTION
Dev. Disable/Test This option enables an individual device that forms part
of the fire system to be Disabled, Activated or put into
Test. The status lamps will illuminate/extinguish as
appropriate.
Net. Disable/Test This option enables the user to control individual devices
that are logged onto other control panel’s on the
Networked Fire System. Such as a smoke detector or call
point to be changed from their normal active status, to
be disabled or put into test.
Det Zone Dis/Test This option allows the Detection Zone to be viewed and
altered. The zone can be either Active, Test or Disable. If
any zones on the system are disabled or in test mode the
relevant LED Indicators will light to indicate this.
Alarm Zone Disable This option allows the disablement of groups of sounders
within the system. The Alarm Zone can be either Enabled
or Disabled. If Disabled the relevant LED indicator will
illuminate.
ARE Disable This option allows connection to the Fire Brigade via the
Brigade Relay to be disabled. Therefore any subsequent
fire activation’s will not operate this relay. The panel
operation, although unaffected, will display the text
“ARE/BRIGADE DISABLED” to ensure the system is not
left in this mode.
System Mode This option allows enablement of up to eight different
system modes of operation. These are pre-programmed
and can be changed if required by the
Installer/Maintenance Contractor.
Engineers Config This option when entered prompts for a PIN number to be
entered to Allow access to Level 3. This menu is for
Installer/Maintenance Contractor use only.
Printer Options This option allows the Printer, when fitted, to be both
“Enabled” and “Disabled”. When “Enabled” and the
option is set to ALL, every Event is printed out. This
option can also be set to FIRE, which will then only print
Fire Events.