Specifications

EMS 5000 FIREPOINT
ENGINEERS OPERATING GUIDE, ISSUE 3.0 – 16/08/10
31
12
Press the “YES” key to toggle though the
device numbers until you get to the
sounder that requires testing. (e.g. 025)
13
Press the key once and the screen will
display:
14
Press the “YES” key to toggle though the
different types of action commands. (E.g.
press the “YES” key seven times takes you to
test
)
There are 11 different types of actions: -
a
EVAC:
The selected sounder will activate with the evac tone.
b
ALERT
The selected sounder will activate with the warning
tone.
C
BOMB
The selected sounder will activate with the bomb tone.
D
LESS CHNG
The selected sounder will do a set of lesson change
beeps.
E
AUX ON
Not Used.
ALL OFF
The selected sounder will stop sounding. (I.e. Silence).
G
RX TEST
The receiver in the selected sounder will be sent a test
message, the sounder will receive the message and send
an acknowledgement message back to the 5000 panel.
H
TEST
The selected sounder will sound for four seconds and
then turn off. The sounder will listen to it self and send
an acknowledgement message back to the 5000 panel.
I
SET SYS
The 5000 panel will send a message to the selected
sounder, which sets the system code in the selected
sounder. The sounder then sends an acknowledgement
message back to the 5000 panel.
J
JOIN GRP
The 5000 panel will send the zone information to the
selected sounder, the selected sounder sends an
acknowledgement back to the 5000 panel.
K
SET LS CH
The 5000 panel will send a message to the selected
sounder which enables the lesson change, feature for the
device.
15 Press the key once and the screen will
display:
16 Press the “YES” key and the screen will now
display:
|** Configure ** |
>Sounder : 025 <
|Action : EVAC |
Yes= Select Time
| Sounder : 025 |
>Action : EVAC <
| Do Action |
Yes= Select Time
| Sounder : 025 |
>Action : TEST <
| Do Action |
Yes= Select Time
| Action : TEST |
>Do Action <
| ^^^^^^^^^^^^^^^ |
Yes= Select Time
Device 025 Timer 9
Retry 07 REPLY NONE
Push Any Key Time