5000 ENGINEERS OPERATING GUIDE
EMS 5000 FIREPOINT Table of Contents Section Page No 1. HOW TO RESET FIRE & FAULT EVENTS. ............................................................................ 6 2. HOW TO ENTER THE SYSTEM EVENT LOG ......................................................................... 7 3. HOW TO ENTER THE SYSTEM EVENT LOG WITH FAULTS DISPLAYED.................................... 8 4. HOW TO DISABLE DEVICES ............................................................................................ 9 5.
EMS 5000 FIREPOINT SYSTEM 5000 VHF Helical Aerial (R/X) Yellow Display UHF Helical Aerial (T/X) Green “∆” & “∇” Arrows For scrolling up and down the menus Zoned LED for Fire Indication Thermal Printer Keypad & Panels Control Key switch CONTROL PANELS ARE SUPPLIED WITH ALL DETECTOR ZONES IN TEST. PLEASE REFER TO SECTIONS 12 OR 14 IN THIS MANUAL TO MAKE ACTIVE. ENGINEERS OPERATING GUIDE, ISSUE 3.
Pins & Access User Log On View Users Change PIN Add 6 Digit User Add 4 Digit User Edit User Delete User Access And Buzzer User Options Order Front Screen Text Site Address Text Delete All Users! EMS 5000 FIREPOINT Options Menu Structure Key in “OFF” position with Password Entered: - Time/Date Set the Time View the Date Set the Date View BST/GMT Set BST/GMT Day-Night Ctrl Event Logging View Log At Date View Entire Log View Log Group Print Log By Date Print Entire Log Processor Resets Options Passwords
EMS 5000 FIREPOINT 1. How To Reset Fire & Fault Events. To reset fires/faults on the 5000 FirePoint, insert the Key into the Panel’s Control Key switch, located at the right of the Panel. Turn the Key to the “ON” Position. Step No 1 Action Screen Display 01 FIRE ALARM TOT 01 RADIO CALLPOINT This a normal Fire Event ZONE 01 2 3 4 Press the “SILENCE ALARMS” button and the screen will now briefly display: (Press Any Key).
EMS 5000 FIREPOINT 2. How To Enter The System Event Log To enter the Systems Event Log on the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the panel. Turn the key to the”ON” position.
EMS 5000 FIREPOINT 3. How To Enter The System Event Log With Faults Displayed To enter the system event log on the 5000 FirePoint with faults displayed there are two ways. The first way is to disable the devices that are in fault then enter the logging in the first menu. The second way is to enter the engineer’s menu main. To enter the engineer’s main menu insert the key into the Panels Control Key switch, located at the right of the Panel and turn it to the “ON” position.
EMS 5000 FIREPOINT 11 12 Press the “YES” key and the screen will now display: Enter the required date to view in dd/mm/yy format, (e.g.28/05/03) then press the “YES” key and the screen will now display: Enter the date to View: / / Yes = Finish ---------------On 28/05/03 At 00:00 New Day of 28/05/03 Yes = Select The log for the date selected can be viewed by using the “∆ ∆” & “∇ ∇” Arrows next to the display, all fire and fault events are listed in date and time order.
EMS 5000 FIREPOINT 8 Press the “∇” key until the screen displays: 9 Press the “YES” key and the screen will now display: 10 Press the “NO” key three times and the screen will now display: 11 Turn the Control key to the “OFF” position and the screen will now display: |Number is: 125 | > Status is: ACTIVE< | Zone is : 01 | Yes= Select Time |Number is: 125 | >Status is :DISABLE< | Zone is : 01 | Yes= Select Time Panel in Access Date Time Status Normal Date Time Note: The “DETECTOR/ZONE DISABLED”
EMS 5000 FIREPOINT 5. How To Re-instate Devices From Disablement To reactivate a device on the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the panel. Turn the key to the “ON” position.
EMS 5000 FIREPOINT 6. How To Disable A Device Across A Network System To disable a device across the network on the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the panel.
EMS 5000 FIREPOINT 11 Press the “0” now display: key and the screen will 12 Enter the device number that you want to Disable (e.g.
EMS 5000 FIREPOINT 7. How To Re-instate a Disabled Device Across a Network To re-instate a Disabled a device across the network on the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the panel.
EMS 5000 FIREPOINT 11 Press the “0” key and the screen will now display: Enter Device (Number 1-256) Number > _ Yes = Finish Time Time Enter the device number that you want to reinstate (e.g.
EMS 5000 FIREPOINT 8. How To Log On A Device To log on a device onto the 5000 FirePoint, take the device in front of the panel. Insert the key into the Panels Control Key switch, located at the right of the Panel.
EMS 5000 FIREPOINT 12 13 Enter the slot number that you want to add a device to (e.g. 125) then press the “YES” key and the Screen will now display: Press the “∇” key until the screen displays: 14 Press the “YES” key and the screen will now display: 15 Take the device you want to log on. Press and hold the logon button for 2-3 seconds (e.g.
EMS 5000 FIREPOINT 16 Press the “YES” key twice and the screen will now display: 17 Press the “NO” key three times and the screen will now display: | Slot is :IN USE | >Logon is DISABLED< | /\/\/\/\/\/\/\/\/\/\ | 01 FAULT TOT 02 Default Device 125 ZONE 01 DEVICE 125 Note: After logging the device on to the system there will be two faults:1st fault is processor reset. (Silence and reset E.G. Page 5) 2nd fault is the Tamper. (Make sure the device tamper is clear then silence and reset E.G.
EMS 5000 FIREPOINT 7 8 9 10 Press 221100 then press the “YES” key and the screen will display: |** Eng.; Config ** | >Device Database < | Sounder Options | Yes= Select Time Press the “∇” key until the screen displays: | Site Survey | > Remove Devices < | Panel Hardware | Yes= Select Time Press the “YES” key and the screen will now display: Enter the device number you want to delete (e.g.
EMS 5000 FIREPOINT 10. How To Replace Devices To replace a device onto the 5000 FirePoint, take the new device in front of the panel. Insert the key into the Panels Control Key switch, located at the right of the panel.
EMS 5000 FIREPOINT 11 Press the “0” key and the screen will now display: Enter Device (Numbers 1-256) Number> Yes= Finish Time 12 Enter the slot number that you want to add a device to (e.g. 125) then press “YES” key and the Screen will now display: |**Logon Options** | >Logon Slot :125 < | Slot is :FREE | Yes= Select Time 13 Press the “∇” key until the screen displays: 14 Press the “YES” key twice and the screen will now display: 15 Take the device you want to log on.
EMS 5000 FIREPOINT 16 Press the “YES” key once and the screen will now display: 17 Press the “NO” key three times and the screen will now display: | Slot is :IN USE | >Logon is DISABLED< | /\/\/\/\/\/\/\/\/\/\ | 01 FAULT TOT 02 Default Device 125 ZONE 01 DEVICE 125 Note: After logging the device on to the system there will be two faults: 1st fault is processor reset. (Silence and reset E.G. Page 3) 2nd fault is the Tamper. (Make sure the device tamper is clear then silence and reset E.G.
EMS 5000 FIREPOINT 11. How To Put Detector Zones Into Test (Testing Devices) To put zones into test for the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the panel. Turn the key to the “ON” position.
EMS 5000 FIREPOINT 11 12 Press the “∇” key and the screen will now display: (Make note of the status the zones is in e.g.
EMS 5000 FIREPOINT 12. How To Take Detector Zones Out Of Test To take zones out of test and back into original state i.e. all on the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the Panel. Turn the key to the “ON” Position.
EMS 5000 FIREPOINT 11 Press the “∇” key once and the screen will now display: | Zone is : 02 | > Status : Test < |^^^^^^^^^^^^^^^^ | Yes= Select Time 12 Press the “YES” key twice and the screen will now display: (notice as the “YES” key is pressed the status changes) | Zone is : 02 | > Status : ACTIVE< |^^^^^^^^^^^^^^^^ | Yes= Select Time This needs to be repeated until all the zones are set back to all, then continue to step 18.
EMS 5000 FIREPOINT Press Number 8 on the keypad and the screen will now display: (number is a quick move key that take you to the bottom of the menu) | Reset System | >Lan Options < |^^^^^^^^^^^^^^ | Yes= Select Time 8 Press the “∆” key once and the screen will now display: | Reset Security | > Reset System < | Lan Options | Yes= Select Time 9 Press the “YES” on the Keypad display: followed “0” key screen will now |** Main Menu ** | > Pins & Access < | System Support | Yes= Select Time 10 Press Nu
EMS 5000 FIREPOINT 14. How To Take All The Zones Out Of Test Across A Network How to take all the zones out of test across a network (depending on which version of software) on the 5000 FirePoint, insert the key into the Panels Control Key switch, located at the right of the panel.
EMS 5000 FIREPOINT 11 Press the “YES” key and the screen will now display: |** Lan Fire DB ** | >H/W Local Panels < | Mimic | Yes= Select Time | Mimic | >Advanced < | ^^^^^^^^^^^^^^ | Yes= Select Time 12 Press the “∇” key until the screen displays: 13 Press the “YES” key and the screen will now display: |*** Advanced *** | > Get Slave Bus Lsts < | ^^^^^^^^^^^^^^^ | Yes= Select Time 14 Press the “∇” key until the screen displays: | Local Mimic | > Set Det.
EMS 5000 FIREPOINT 15. How To Test Individual Sounders To test individual sounders on the 5000 FirePoint, Insert the key into the Panels Control Key switch, Located at the right of the panel.
EMS 5000 FIREPOINT 12 Press the “YES” key to toggle though the device numbers until you get to the sounder that requires testing. (e.g. 025) |** Configure ** | >Sounder : 025 < |Action : EVAC | Yes= Select Time 13 Press the “∇” key once and the screen will display: | Sounder : 025 | >Action : EVAC < | Do Action | Yes= Select Time 14 Press the “YES” key to toggle though the different types of action commands. (E.g.
EMS 5000 FIREPOINT This timer will count down to 0, when the timer reaches 0 the retry should change to 6 and a message is sent to the sounder. If not, that means the panel is still busy and the timer will start again, when the retry number decreases listen for the selected sounder to activate. When the selected sounder has activated it sounds for four seconds and resets itself, watch the display for the acknowledgement message.
EMS 5000 FIREPOINT 4 Press the “YES” key and the screen will now display: 5 Press the “∇” key until the screen displays: 6 Press the “YES” key and the screen will now display: |** Fire system ** | >Dev. Disable/Test < | Net. Disable/Test | Yes= Select Time | System Mode | >Engineers Config < | Printer Options | Yes= Select Time Enter Your PIN For Access> Then Press YES Time Press 221100 then press the “YES” key and the screen will display: |** Eng.
EMS 5000 FIREPOINT KEY 0 4 5 6 7 8 9 NO YES FUNCTION Enters a blank space into the new device name being entered. Moves the alphabet wheel of characters to the Left, by one character space at a time. Enters the character in the centre directly above the character selector |. Moves the alphabet wheel of characters to the Right, by one character space at a time. Moves the flashing cursor to the left, through the new device name by one character space at a time.
EMS 5000 FIREPOINT 18. Fault List Panel Faults MN BT AT Description In Log Mains Input Failed. Battery Charging Fail. Main Receiver, Aerial Tamper.
EMS 5000 FIREPOINT 19. Do’s and Don’ts Don’t place any aerials near metal work and keep aerials 2 meters away from all electrical equipment, all tips of aerials must stay away from any obstruction. Always pinch and twist on helical aerials to ensure good connection. Always make sure the correct aerial is on the right side of the panel by matching the coloured bands of the aerial to the colours on the panel. When testing devices, always put the zones into test so sounders are not activated.
EMS 5000 FIREPOINT ENGINEERS OPERATING GUIDE, ISSUE 3.
EMS 5000 FIREPOINT ENGINEERS OPERATING GUIDE, ISSUE 3.
EMS 5000 FIREPOINT Dealer Information: EMS Group Head Office Technology House, Sea Street Herne Bay, Kent CT6 8JZ England Tel: +44 (0) 8712 710804 Fax: +44 (0) 1227 369679 Email: enquiries@emsgroup.co.uk The information contained within this literature is correct at time of publishing. The EMS Group reserves the right to change any information regarding products as part of its continual development enhancing new technology and reliability.