Installation manual
EMS 5000 FIREPOINT
4
INSTALLATION MANUAL, ISSUE 3.0 – 16/08/10
4. Installation
Following the Site Survey, System Control Panels should be positioned as stated
considering:-
The recommended minimum distance between metal objects or equipment for the aerial
is 400mm.
The recommended minimum distance to any electrical equipment is 2 metres, (See
Figure 1).
5. Control Panel - Removing Items before Mounting
Before mounting the unit, it is necessary that certain items be removed, so as to prevent
the risk of damage to the internal circuitry.
Remove the Door Assembly from the Back Box. To achieve this, disconnect the Ribbon
Cables and Earth links, loosen the hinge screws on the Back Box side of the hinge and
pull the door away. Ensure that the Door Assembly is suitably stored and that ESD
precautions are observed (see Figure 2).
Establish the required cable entries. Knockouts should be made prior to fixing the Back
Box to the wall.
Ensure that the Back Box is free of swarf and other debris.
6. Mounting the Enclosure to a Wall
It is recommended that the Control Panel be mounted in accordance with the site survey
so that the display is at eye level.
Achieve this firstly by securing it to the wall, via the single fixing “keyhole”, located in
the top centre of the box. The box should be hung and levelled, allowing holes to be
marked out for each of the four remaining mounting holes (shown on figure 3).
Once the Back Box is fitted to the wall, all external cabling should be run to the box,
including the provision of an unswitched 240 volt supply. The mains cable should be
dressed away from the main radio PCB and should be as short as possible.
7. Replacing Items after Mounting
Replace the Door assembly by reversing the steps given in Section 5, ensuring that all
electrical connections, including the earth leads, are made.
Ensure that both UHF and VHF aerials are fitted to the top of the Control Panel. To
ensure correct fitment, the aerial identified with the coloured band must be fitted to the
connector identified with the coloured band. If high gain aerials are to be used they must
be positioned in accordance with the site survey.