Installation manual

EMS 5000 FIREPOINT
38
INSTALLATION MANUAL, ISSUE 3.0 – 16/08/10
Multisensor Sounder Set Into SINGLE SMOKE or SINGLE HEAT Mode (5-
5190)
ZR432 In Smoke Only Mode
Sw
1
Sw
2
Sw
3
Sw
4
Sw
5
Sw
6
Sw
7
Mode Of Operation
Off Off Off On Off X Off High Sensitivity
On Off Off On Off X Off Normal Sensitivity
Off On Off On Off X Off Low Sensitivity
On On Off On Off X Off Low Sensitivity + AVF
ZR432 In Heat Only Mode
Sw
1
Sw
2
Sw
3
Sw
4
Sw
5
Sw
6
Sw
7
Mode Of Operation
Off Off Off Off On X Off 58ºC ROR
On Off Off Off On X Off 58ºC fixed
Off On Off Off On X Off 70ºC fixed
On On Off Off On X Off 82ºC fixed
X – Not Used
AVF – Average
ROR – Rate Of Rise
Dip Switches 1 & 2 remain as heat level/optical sensitivity settings
Dip Switch 3 has no effect whilst single detector mode
Dip Switches 4 & 5 are heat and smoke settings.
Dip Switch 7 is OFF compatibility mode disabled.
Multisensor Sensitivity
The Multisensor set into single heat mode has new specified sensitivity levels of
detection. These are supported by current standards (EN54 part 7).
Multisensor Set into Both SMOKE & HEAT Mode
ZR432 in Dual Mode
Sw
1
Sw
2
Sw
3
Sw
4
Sw
5
Sw
6
Sw
7
Heat
Band
Optical
Sensitivity
Off Off Off On On X Off 58ºC Normal
On Off Off On On X Off 58ºC Medium
Off On Off On On X Off 58ºC Low
On On Off On On X Off 58ºC Low+AVF
Sw
1
Sw
2
Sw
3
Sw
4
Sw
5
Sw
6
Sw
7
Heat
Band
Optical
Sensitivity
Off Off On On On X Off 72ºC Normal
On Off On On On X Off 72ºC Medium
Off On On On On X Off 72ºC Low
On On On On On X Off 72ºC Low+AVF