22 EMPYRE ELITE XT INSTALLATION AND OPERATION MANUAL
Operating the Digital Temperature Switch (DTS)
DTS Description
The digital temperature switch is designed for many
heating and cooling applications. The probe temperature
(Figure 1) is displayed on the bright 3-digit, red light
emitting diode (LED). The user is able to adjust the
damper on-off temperature set points using the front
keypad. The unit features a 16 amp, single pole, double
throw (SPDT) relay with the temperature display in
degrees Fahrenheit.
DTS Wiring Diagram
DTS Display Messages
In normal operation, the probe temperature will be
shown on the display. In case of an alarm or error, the
following messages will be shown:
Er = Memory error
- - = Short-circuit probe error
∞=Openprobeerror
DTS Technical Data
Accuracy: ±1°
Output: 16 Amp 1HP 240 Vac SPDT relay
Supply voltage: 115 Vac ± 10%
Display: 3-digit, red.
DTS Programming
• PressSET.SPtextwillappearonthedisplay.
• Press SET again. The real value is shown on the
display.
• ThevaluecanbemodiedwiththeUPandDOWN
arrows.
• PressSETtoenternewvalues.
• Press SET and DOWN at the same time to exit
programming or wait one minute and the display
will automatically exit the programming mode.
NOTE: Only the temperature setting is programmable.
All other settings are locked.
DTS Maintenance/Repair
Afternalinstallationofthedigitaltemperatureswitch,
no routine maintenance is required. This device is not
eldrepairableandshouldbereturnedtothefactoryif
recalibration or other service is required.
Anymodicationortamperingwiththefactorysettings
of the DTS will void the furnace warranty.
Figure 1