Owner`s manual
32084-3-0813Page 36
INITIAL STARTUP AND ADJUSTMENTS
WALL FURNACE INSTALLATION
The table below outlines the BTU input rate of the wall furnace for
each ame level.
Heat Level BTU Input
Single Tube
BTU Input
Double Tube
5 (HI) 17,500 35,000
4 15,350 30,700
3 13,150 26,300
2 10,950 21,900
1 (LO) 8,750 17,500
Table 4
7. After 45 to 70 seconds, the circulating air blower will acti-
vate. The circulating air blower speed will be set by the heat
level and will display on the display. See Figure 59.
Figure 59
Display Backlight
The display panel back light will automatically turn off ve seconds
after an input (either manual or remote) is acknowledged. The back
light will automatically turn on when a new input is acknowledged.
To turn the back light on manually, press the “Backlight” button on
the bottom left of the display panel. See Figure 24, page 18.
Shut Down Instructions
To off turn the wall furnace, simply set the thermostat to a set-
ting below the room temperature or push the display panel’s mode
select button to “OFF”. See Figure 15, page 11. DO NOT cut the
main electrical power to the wall furnace.
The circulating air blower will continue to operate after the burner
is turned off. The blower will stop automatically after 100 to 160
seconds to ensure the wall furnace has cooled sufciently.
Checking Manifold Pressure
Both Propane and Natural gas valves have a built-in pressure
regulator in the gas valve. See page 22 for a list of the normal high
and low manifold pressures.
A pressure tap accessible for test gauge connection is located on
the outlet side of the gas control.
Blower Operation
The circulating air blower will automatically engage and increase
in speed depending on the heat level. The circulating air blower
will start 45 to 70 seconds after ignition of the burner.
Once the wall furnace is turned off or the call for heat has been
satised, the circulating air blower will continue to run. The blower
will automatically turn off 100 to 160 seconds after the wall furnace
turns off to ensure proper cooling of the wall furnace.