Owner`s manual
32084-3-0813Page 30
The PVSA1 Air Pipe Kit is required for installation of the wall fur-
nace in a direct-vent conguration. See Page 15.
Max Vent Run - 50 ft. Equivalent
When installing a horizontal vent termination, the minimum vent
length protruding from the outside wall is 10 inches (304mm) for
exhaust and six inches (152mm) for intake air. See Figure 47.
For venting, cap exhaust with 45° elbow and intake air with 90º
elbow both pointed downward.
Notice: All horizontal runs require a 1/4” per foot rise to run con-
densation back to the wall furnace.
Notice: For each 45° elbow installed, reduce the length of the
run MUST be reduced by 1.5 feet (45 cm). Reduce the length
of the run three feet (91.4 cm) for every 90° elbow. The vent
terminal elbow does not contribute to the overall vent length
measurement.
Figure 47
Figure 48
Figure 49
The measurement for center to center of the pipes can be 5” to
24” maximum.
DIRECT VENT EXAMPLES
WALL FURNACE INSTALLATION
Optional Deep shroud kit
shown for vent run in front of
wall. See page 15.