VENTING
Due to the high efciency of the Ultra Saver, condensate will form
in the heat exchanger and ue pipe. A condensate trap and drain
tube are provided to dispose of the condensate to a nearby oor
drain. An optional humidication tray is also available to evapo-
rate the condensate back into the room as humidity instead of
draining it away from the wall furnace. See page 15.
If draining the condensate away from the wall furnace, route the
condensate drain tube provided in the instruction envelope to the
elbow on the tube sticking through the back of the wall furnace
to a nearby drain. See Figure 41. The elbow may be rotated to
direct the hose to either side or straight down. Eliminate all sags
or dips as they may prevent drainage. An optional drain tube
extension kit and optional condensate pump kit accessory are
available. See page 15.
Notice: Due to the mildly acidic nature of wall furnace condensa-
tion, check with local authorities to determine if a ph neutralizing
process may be required.
Figure 41
WALL FURNACE INSTALLATION
Carefully push the wall furnace back into position against the rear
shroud and connect the ue pipe to the inducer.
Secure wall furnace to the rear shroud by using four 10 x 1/2”
(13mm) hex-head screws previously removed (see page 21). See
Figure 42.
Figure 42
Notice: For oor mounted wall furnaces, ensure the adjustable
legs are all on the oor.
To complete inside installation, tighten the inducer hose clamp
with a 10-inch 5/16” nut driver. See Figure 43.
Figure 43