Owner`s manual

32084-6-0214 Page 27
VENTING
Due to the high efciency of the Ultra Saver, condensate will form
in the heat exchanger and ue pipe. A condensate trap and drain
tube are provided to dispose of the condensate to a nearby oor
drain. An optional humidication tray is also available to evapo-
rate the condensate back into the room as humidity instead of
draining it away from the wall furnace. See page 15.
If draining the condensate away from the wall furnace, route the
condensate drain tube provided in the instruction envelope to the
elbow on the tube sticking through the back of the wall furnace
to a nearby drain. See Figure 41. The elbow may be rotated to
direct the hose to either side or straight down. Eliminate all sags
or dips as they may prevent drainage. An optional drain tube
extension kit and optional condensate pump kit accessory are
available. See page 15.
Notice: Due to the mildly acidic nature of wall furnace condensa-
tion, check with local authorities to determine if a ph neutralizing
process may be required.
Figure 41
WALL FURNACE INSTALLATION
Carefully push the wall furnace back into position against the rear
shroud and connect the ue pipe to the inducer.
Attach the wall furnace to the rear shroud by using four 10 x 1/2”
(13mm) hex-head screws previously removed (see page 21). See
Figure 42. Do not tighten the screws.
Reinstall the lter door by inserting the lter door tabs into the
two receiving slots on top of the rear shroud. Close the lter door,
then adjust the wall furnace positions to minimize the gap be-
tween the wall furnace casing and the lter door. Tighten the four
wall shroud screws to secure the wall furnace in place.
Figure 42
Notice: For oor mounted wall furnaces, ensure the adjustable
legs are all on the oor.
To complete inside installation open the lter door and, tighten
the inducer hose clamp with a 10-inch 5/16” nut driver. See
Figure 43.
Figure 43