Before installing in a solid fuel burning replace, the chimney ue
and rebox must be cleaned of soot, creosote, ashes and loose
paint by a qualied chimney cleaner.










1. Center the gas log in the replace or rebox. The grates must
clear the replace or rebox screen.
2. An anchor hole is provided in the two bottom side members of
the grate frame. After centering the grate correctly, mark the
hole positions on the replace/rebox oor. Drill two (2) 5/32"
diameter holes approximately 1-1/2" deep for masonry screws
or 1/8" hole for sheet metal screws.
3. Anchor the grate to the replace/rebox oor using the screws
provided.
-


BEFORE FULLY INSTALLING THE APPLIANCE
FOR FACTORY BUILT FIREPLACES
-
     -
PLIANCES FOR INSTALLATION IN SOLID FUEL BURNING


20 30 40 50 60 70 80
Chimney
Height*
(ft)

10 11.3 16.6 22.1 28.3 35.3 44.2 -
15 8.6 12.6 17.3 21.2 26.4 32.2 31.2
20 7.5 10.8 14.5 18.1 22.1 26.4 31.2
25 6.6 9.6 12.6 15.9 18.1 22.9 27.3
30 6.2 9.1 11.3 14.5 17.3 20.4 24.6
35 5.7 8.0 10.8 13.2 15.9 18.9 22.1
40 5.3 7.5 10.2 12.6 15.2 18.1 20.4

5.9 8.8 11.7 14.6 17.6 20.5 23.4
Chimney
Height*
(m)

3.05 72.9 107.1 142.6 182.6 227.8 285.2 -
4.57 55.5 81.3 111.6 136.8 170.3 207.8 248.4
6.10 48.4 69.7 93.6 116.8 142.6 170.3 201.3
7.62 42.6 61.9 81.3 102.6 116.8 147.8 176.1
9.14 40.0 58.7 72.9 93.6 111.6 131.6 158.7
10.67 36.8 51.6 69.7 85.2 102.6 121.9 142.6
12.19 34.2 48.4 65.8 81.3 98.1 116.8 131.6
* Height is from hearth to top of chimney and the minimum height is
10 feet (3.05m).
** Chart shows minimum opening (sq. in.) (cm
2
) for given height and
input rate.

-
-


20 30 40 50 60 70 80
Chimney
Height*
(ft)

6 17.6 25.7 33.8 41.7 49.2 56.6 64.0
8 16.5 23.7 31.2 38.7 45.5 52.4 59.7
10 15.1 21.7 28.7 35.2 41.7 48.2 54.3
15 14.1 19.9 26.1 32.0 37.7 43.2 48.8
20 12.9 18.5 23.7 28.8 34.3 39.8 44.4
30 12.2 16.9 21.6 26.5 31.2 35.9 40.3

5.9 8.8 11.7 14.6 17.6 20.5 23.4
Chimney
Height*
(m)

1.83 113.6 165.8 218.1 269.0 317.4 365.2 412.9
2.44 106.5 152.9 201.3 249.7 293.6 338.1 385.2
3.05 97.4 140.0 185.2 227.1 269.0 311.0 350.3
4.57 91.0 128.4 168.4 206.5 243.2 278.7 314.8
6.10 83.2 119.4 152.9 185.8 221.3 256.8 286.5
9.14 78.7 109.0 139.4 171.0 201.3 231.6 260.0
* Height is from hearth to top of chimney and the minimum height is 6
feet (1.83m).
** Chart shows minimum opening (sq. in.) (cm
2
) for given height and
input rate.