Owner`s manual
29898-8-1114 Page 9
The space in the above example is a conned space because the
actual BTU/Hr used is more than the maximum BTU/HR the space
can support. You must provide additional fresh air. Your options
are as follows:
A. Rework worksheet, adding the space of an adjoining room. If
the extra space provides an unconned space, remove door
to adjoining room or add ventilation grills between rooms. See
VentilationAirFromInsideBuilding.
B. Vent room directly to the outdoors. See VentilationAirFrom
Outdoors.
C. Install a lower BTU/Hr heater, if lower BTU/Hr size makes room
unconned.
If the actual BTU/Hr used is less than the maximum BTU/Hr the
space can support, the space is an unconned space. You will need
no additional fresh air ventilation.
WARNING:Youmustprovideadditionalventilationairin
aconnedspace.
Ventilation Air
VentilationAirFromInsideBuilding(Figure1)
This fresh air would come from an adjoining unconned space. When
ventilating to an adjoining unconned space, you must provide two
permanent openings: one within 12" of the ceiling and one within
12" of the oor on the wall connecting the two spaces (see options
1 and 2, Figure 1). You can also remove door into adjoining room
(see option 3, Figure 1). Each ventilation grill or opening shall have
a minimum free area of one square inch per 1,000 BTUH of the total
input rating of the gas equipment in the conned space.
12”
(305mm)
OPTION 1:
VENTILATION GRILLS
INTO ADJOINING ROOM
12”
(305mm)
OPTION 2: VENTILATION GRILLS
INTO ADJOINING ROOM
OPTION 3: REMOVE DOOR INTO ADJOINING ROOM
Figure 1
WARNING: Rework worksheet, adding the space of the
adjoiningunconnedspace.Thecombinedspacesmust
have enough fresh air to supply all appliances in both
spaces.
VentilationAirFromOutdoors(Figure2)
Provide extra fresh air by using ventilation grills or ducts. You must
provide two permanent openings: one within 12" of the ceiling and
one with 12" of the oor. Connect these items directly to the outdoors
or spaces open to the outdoors. These spaces include attics and
crawl spaces. In most cases for direct communication with the
outdoors or direct communication through a vertical duct a free
area opening of one square inch per 4,000 BTU/Hr of heater input
rating for each grill. If a horizontal duct is used, a grill free area or
duct opening shall have a free area opening of one square inch per
2,000 BTU/Hr for each grill. Follow the National Fuel Code ANSI
Z223.1/NFPA54, Air for Combustion and Ventilation for required
size of ventilation grills or ducts.
IMPORTANT: Do not provide openings for inlet or outlet air into attic
if attic has a thermostat-controlled power vent. Heated air entering
the attic will activate the power vent.
OUTLET
AIR
OUTLET
AIR
VENTILATED
ATTI C
INLET
AIR
TO
ATTI C
TO
CRAWL
SPACE
INLET
AIR
VENTILATED
CRAWL SPACE
Figure 2
PROVISIONS FOR ADEQUATE COMBUSTION & VENTILATION AIR (continued)