User Manual
Analog Input Specific Addresses:
Parameter
AI1 AI2 AI3 AI4 AI5 Default
Configuration Bits
40123 40133 40143 40153 40163 0
Minimum Scale Value
40124 40134 40144 40154 40164 0
Maximum Scale Value
40125 40135 40145 40155 40165 0
Scaled Value
30064 30070 30076 30082 30088 -
Analog Input Configuration Bits:
AI1 AI2 AI3 AI4 AI5 Description
40123.0
bit
40133.0
bit
40143.0
bit
40153.0
bit
40163.0
bit
4-20mA/2-10V Select:
0 = 0-20 mA/0-10 V
1 = 4-20 mA/2-10 V
The Scaled Value for analog inputs is calculated according to the state of the 4-20mA / 2-10V Selection
configuration bit.
Analog Output Specific Addresses:
Parameter
AO1 AO2 Default
Minimum Scale Value for Input
40173 40183 0
Maximum Scale Value for Input
40174 40184 20000
Minimum Scale Value for Output
40175 40185 0
Maximum Scale Value for Output
40176 40186 10000/20000
Analog Output Function
0: Manual use
1: Using the scale values above, it reflects the input to the output.
2: It drives the analog output as PID output, using the minimum and
maximum scale parameters for the output.
40177 40187 0
In case the analog output function parameter is set to 1 or 2;
- AI1 is used as input for A01 output.
- AI2 is used as input for A02 output.
* Not: Mirroring the input to output feature (Analoque Output Function = 1) cannot be used in modules
with PT100 inputs.
11 EN PROOP-IO 02 V08_1221