User Manual
The conversion of the values read from the module according to the analog input type is described in the
following table:
Analog Input The Value Range Conversion Factor Example of value shown in PROOP
PT-100
-200° – 650°
-2000 – 6500 x10
-1
Example-1: The read value as 100 is converted to
10
o
C.
Example-2: The read value as 203 is converted to
20.3
o
C.
0 – 10V
0 – 20000 0.5x10
-3
Example-1: The read value as 2500 is converted
to 1.25V.
0 – 50mV
0 – 20000 2.5x10
-3
Example-1: The read value as 3000 is converted
to 7.25mV.
0/4 – 20mA
0 – 20000 0.1x10
-3
Example-1: The read value as 3500 is converted
to 7mA.
Example-2: The read value as 1000 is converted
to 1mA.
The conversion of the values write at the module according to the analog output type is described in the
following table:
Analog Output The Value Range Conversion Rate Example of Value Written in Modules
0 – 10V
0 – 10000 x10
3
Example-1: The value to be written as 1.25V is
converted to 1250.
0/4 – 20mA
0 – 20000 x10
3
Example-1: The value to be written as 1.25mA is
converted to 1250.
10 EN PROOP-IO 02 V08_1221