Instructions

Alarm off delay time for Alarm Output-1. It can be adjusted from 0000 to
9998 seconds. When the value is greater than 9998, is seen on
the screen. It means alarm latching output is selected. It is active if logic
output function of Alarm Output-1 is alarm output.
it can be adjusted from 0% to 50% of process input scale
( - ) It is active if logic output function of Alarm Output-1 is
alarm output.
59
Alarm- 1 hysteresis value.
Alarm on delay time for Alarm Output-1. It can be adjusted from 0000 to
9999 seconds. It is active if logic output function of Alarm Output-1 is
alarm output.
Alarm
Status
Alarm
Output
On
Delay
OFF
Delay
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process
Set
Process Set + Alarm Set
Alarm
Output
Process Value
HYS
ON
OFF
Process
Set
Process Set - Alarm Set
Alarm
Output
Process Value
HYS
Process Set - Alarm Set
HYS
ON
OFF
Process
Set
Process Set + Alarm Set
Alarm
Output
Process Value
Deviation low alarm
Deviation band alarm
Deviation range alarm
It can be adjusted from 0 to 99 seconds. Active if logic output
function of Alarm-1 Output is alarm output. After the unit is power-on
and Alarm Stabilisation Time is expired, if an alarm condition which
is selected with Alt1 is present, then Alarm-1 output becomes active.
Alarm Output-1 Alarm Stabilization Time