Instructions

SENSOR BREAK OUTPUT VALUE
(FOR HEATING PID 0.0%, 100.0%)
(FOR COOLING PID -100.0%, 0.0%)
When sensor breaks, controlling of the process can continue by entering %output
value to parameter.
If this parameter 0.0, process control output does not perform an output when
sensor breaks.
If > 0
56
If < 0
Process
Output
100%
50%
0%
Process
Value
Process
Output
100%
50%
0%
Process
Value
Set Value
( )
Cooling Set
Value
( + )
Set Value
( + )
Heating Set
Value
( )
Soft Start Set value
Soft Start Control Output
It can be adjusted from 10% to 90% with increment and decrement buttons.
Soft Start Control Period
It can be adjusted from 1 to 100 sec with increment and decrement buttons.
It can be adjusted from 0 to 9999 with increment and decrement buttons. If parameter
is selected , Soft start function becomes inactive. When the device power on, if
the Soft start set value different from and temperature value is lower than soft
start value on heating processes, device starts soft start operation, until temperature
reaches soft start set value. On soft start device output period is SSCt parameter
value and device control output is SSCo parameter value.