6.2.1 Selection of PID Tune and Operation Form
6.2 Technician Parameters
TUNE SELECTION
By selecting one of the methods below, device can determine the PID
parameters.
Self tune (Step Response Tuning) operation
Device operates according to the defined PID
parameters
Auto tune (Limit Cycle Tuning) operation
Auto-Self Tune
Self Tune operation is performed, if the conditions are
realized when power on firstly. In normal operation, it
controls the tune conditions in Auto Tune selection which
explained below. If any of the conditions is realized, it
performs the Auto Tune operation.
AUTOMATIC TUNE SELECTION
i
Device does not do (Limit Cycle Tuning) operation
or while operation runs, this selection is adjusted
and Auto Tune operation is canceled.
If parameter is or , when the conditions
for Auto Tune parameter that are explained in Tune
Methods section are realized, it starts to perform Auto
Tune (Limit Cycle Tuning) operation.
By pressing AT button, Automatic Tune can be selected or
For being able to use AT button, AT (Auto Tune) Button protection parameter
must be . (For details, refer to Section 6.2.8 General Parameters)