Operation type selection parameter of output-2.
THIS PARAMETER IS NOT ACTIVE IN DEVICES WITH ONE RELAY.
Operation Type of Output-2 relay can be adjusted as
“HEATING”. Normally energised.
Operation Type of Output-2 relay can be adjusted as
“COOLING”. Normally de-energised.
Process Offset Parameter (Default = 0).
This parameter is offset for the process value. This defined value is added to
the process value.
-10 to 10 °C for TC Type Devices,
-10 to 10 °C for PT-100 (0°C , 400°C),
-10.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C),
-10 to 10 °C for PTC (-50°C, 150°C),
-10.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
-10 to 10 °C for NTC (-50°C, 100°C)
Minimum Pulling Time Parameter for Output-1 (Minimum Off Time)
(Default = 0)
When Output-1 is inactive this time must be expired for Output-1 to become
active again. It can be adjusted from 0 to 100 seconds
42
i
“Hs2” and “rL2” PARAMETERS ARE ACTIVE IN DEVICES WITH TWO RELAYS.
If no operation is done in programming or Set value mode for 20 seconds, device
turns to main operation screen automatically.
Programming Mode Accessing Password ( Default =0 )
It is used for accessing to the programming mode. It can be adjusted from 0 to
999. If it is selected 0, password is not entered for accessing to the
parameters.