Instructions
Table Of Contents
- Page 1
- Page 2
- Page 3
- Page 4
- Page 5
- Page 6
- Page 7
- Page 8
- Page 9
- Page 10
- Page 11
- Page 12
- Page 13
- Page 14
- Page 15
- Page 16
- Page 17
- Page 18
- Page 19
- Page 20
- Page 21
- Page 22
- Page 23
- Page 24
- Page 25
- Page 26
- Page 27
- Page 28
- Page 29
- Page 30
- Page 31
- Page 32
- Page 33
- Page 34
- Page 35
- Page 36
- Page 37
- Page 38
- Page 39
- Page 40
- Page 41
- Page 42
- Page 43
- Page 44
- Page 45
- Page 46
i
5. Parameters
5.1 Set Parameters
SET1
SET2
5.2 Program Parameters
Parameters are divided into two groups as SET and PROGRAM parameters.
SET value for Output-1. Control of output-1 relay is done according to this
value.
This value can be adjusted according to input type, minimum and maximum
of scale.
SET value for Output-2. Control of output-2 relay is done according to this
value.
This value can be adjusted according to input type, minimum and maximum
of scale.
THIS PARAMETER IS NOT ACTIVE IN DEVICES WITH ONE RELAY.
Operation Type Selection parameter for output-1.
Operation type of output-1 relay can be adjusted as
“HEATING”. Normally energised.
Operation type of output-1 relay can be adjusted
“COOLING”. Normally de-energised.
“Hs2” and “rL2” PARAMETERS ARE ACTIVE IN DEVICES WITH TWO RELAYS.
If no operation is done in programming or Set value mode for 20 seconds, device
turns to main operation screen automatically.
41
Hysteresis Parameter for Output-1 ( Default = 3 )
1 to 100 °C for TC Type Devices,
1 to 100 °C for PT-100 (0°C , 400°C),
1.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C),
1 to 100 °C for PTC (-50°C, 150°C),
1.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
1 to 20 °C for NTC (-50°C, 100°C)
Hysteresis Parameter for Output-2 ( Default = 3 )
1 to 100 °C for TC Type Devices,
1 to 100 °C for PT-100 (0°C , 400°C),
1.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C),
1 to 100 °C for PTC (-50°C, 150°C),
1.0 to 10.0 °C for PTC (-19.9°C, 99.9°C) and NTC (-19.9°C, 99.9°C)
1 to 20 °C for NTC (-50°C, 100°C)