Instructions

ENGLISH
No point
Fixed dual point display adjustment. Display adjustment low
point value is fixed to -1999, display adjustment high point
value is fixed to 9999.
Between second and third digits “0.00”
User can do defined 16 display adjustment points.
Between third and fourth digits “0.000”
Between first and second digits “0.0”
User can do dual point display adjustment with tPoL and tPoH.
Display Point Position
This parameter is active if oltage/Current input is selected.ZV
Display Value Adjustment Type
This parameter is active if oltage/Current input is selected.ZV
Low Point Display adjustment (-1999, 9999)Unit
This parameter is active if oltage/Current input is selected.ZV
High Point Display adjustment (-1999, 9999)Unit
This parameter is active if oltage/Current input is selected.ZV
Display adjustment points (-1999, 9999)Unit
This parameter is active if oltage/Current input is selected.
In multi point display adjustment operation, defined scale is
divided into 16 adjustment points.
For example : is (0-50 mV ) .
ZV
Z
mV Z
50
Po00 = 0
Po01
Po02
Po03
Po04
Po05
Po16
Po06
Po15
Po07
Po08
Po09
Po10
3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125 3.125
3.125 6.25 9.375 12.5 15.625 18.75 21.825 25 28.125 31.25 34.375 37.5 40.625 43.75 46.875
Po14
Po13
Po12
Po11
Process
Set value
0-50 mVZ range are divided into 16 egual parts. Every “Poxx” SET value is defined
50 / 16 = 3.125 mVZ range.
11