Instructions
MotorizedValveControl
ElectricalWiringDiagramfor
ESM-7750.1.20.1.1/01.00
NOC
RelayOutput
Module
EMO-700
5A@250V V
Max.50mA
TC
Pt-100
0to20mA Z
0to50mV
0to10V
Z
Z
1
10
2
11
3
12
4
13
5
14
6
15
MODULE-1
MODULE-2
7
8 9
16 17 18
a
Input/
Output
Module-2
N L
M
~
Opening
Relay
Max.5A T
Fuse
V
V V
100...240V V 50/60Hz
1A TV
5A@250V V
OUTPUT-3
CNCNO
Motorized valve control can be performed with parameter. For doing this operation, EMO
Relay output module must be plugged in Module-1 socket. Module-1 and output-3 controls
the position of the valve with motorized valve control.
-
700
RELEVANT PARAMETERS:
Parameter
In PASS OPEr or PASS tECH (run
LýSt) menu page ;
: It defines how to
perform the motorized valve control
with the device.
Þ
If motorized valve control is activated
by selecting the parameter
Or
In PASS tECH GEnn COnF menu
page and parameters
are shown.
I t c a n b e
adjusted from 5 to 600. The unit is
“second”.
It defines after how many seconds
valve is completely opened. For
determinig the parameter correctly,
close the valve manually. Be sure
that valve is closed completely, then
open it manually without stopping
and measure that how many
seconds have passed for opening it
completely. Parameter must be
entered measured value+5%of
measured value and as second.
I t c a n b e
adjusted from 0,1 to 5,0. Unit is %. It
is % of Ultt parameter. Minimum
movement steps of valve while
opening or closing are determined as
% ratio. If valve oscillates while
c o n t r o l l i n g , I N C R E A S E t h e
parameter value!
Þ
parameter :
parameter :
MOTORIZEDVALVE
SensorSupply
Voltage
Output-3
Closing
Relay
UniversalProcess
Input
Supply
Switch
Closing
Common
Opening
Valve
Supply
Input
Opening
Closing
Communication
Module
(RS-232(standard)/
RS-485(optional))
Fuse
72
24V 10%Z ±