Instructions

56
SENSOR BREAK OUTPUT VALUE
(FOR HEATING PID 0.0%, 100.0%)
(FOR COOLING PID -100.0%, 0.0%)
When sensor breaks, controlling of the process can continue by entering
%output value to parameter.
If this parameter 0.0, process control output does not perform an output
when sensor breaks.
If > 0 (Dead Band)
If < 0 (Overlap Band)
Process
Output
100%
50%
0%
Process
Value
Heating Set
Value
( )
Cooling Set
Value
( + )
Process
Output
100%
50%
0%
Process
Value
Cooling Set
Value
( + )
Heating Set
Value
( )
Soft Start Set value
It can be adjusted from 0 to 9999 with increment and decrement buttons. If
parameter is selected , Soft start function becomes inactive. When
the device power on, if the Soft start set value different from and
temperature value is lower than soft start value on heating processes,
device starts soft start operation, until temperature reaches soft start set
value. On soft start device output period is SSCt parameter value and
device control output is SSCo parameter value.
Soft Start Control Output
It can be adjusted from 10% to 90% with increment and decrement
buttons.
Soft Start Control Period
It can be adjusted from 1 to 100 sec with increment and decrement buttons.