- Page 61
- Page 62
- Page 63
- Page 64
- Page 65
- Page 66
6.2.5 Process Output Configuration Parameters
It determines output functions of Process Outputs
It determines control algorithms of Process Outputs
Hysteresis value of Process Outputs. It can be adjusted from 0% to
50% of full scale. ( It is active if ON/OFF control is selected )
It determines operation form of hysteresis
( It is active if ON/OFF control is selected)
In ON/OFF operation, this time must be passed for the output to be
energised again. It can be adjusted from 0.0 to 100.0 seconds.
( It is active if ON/OFF control is selected)
Heating
ON/OFF control algorithm
Cooling
PID control algorithm
SV + HYS/2 and SV - HYS/2
SV and SV+HYS or SV and SV-HYS
It determines if Process Output ( SSR Driver Output ) and Alarm
Output-2 operates together or not.
Process Output (SSR Driver Output) and Alarm Output-2
operates separately.
Process Output (SSR Driver Output) and Alarm Output-2
operates together. Alarm functions of Alarm Output-2 can
not be used
57