Instructions
Table Of Contents
- Page 1
- Page 2
- Page 3
- Page 4
- Page 5
- Page 6
- Page 7
- Page 8
- Page 9
- Page 10
- Page 11
- Page 12
- Page 13
- Page 14
- Page 15
- Page 16
- Page 17
- Page 18
- Page 19
- Page 20
- Page 21
- Page 22
- Page 23
- Page 24
- Page 25
- Page 26
- Page 27
- Page 28
- Page 29
- Page 30
- Page 31
- Page 32
- Page 33
- Page 34
- Page 35
- Page 36
- Page 37
- Page 38
- Page 39
- Page 40
- Page 41
- Page 42
- Page 43
- Page 44
- Page 45
- Page 46
- Page 47
- Page 48
- Page 49
- Page 50
- Page 51
- Page 52
- Page 53
- Page 54
- Page 55
- Page 56
- Page 57
- Page 58
- Page 59
- Page 60
- Page 61
- Page 62
- Page 63
- Page 64
- Page 65
- Page 66
43
For Auto Tune ( Limit Cycle Tuning ) operation :
1- Tune slection parameter in “run List” menu must be selected Auto
tune or Auto-Self tune .
2 - For being started Tune operation (Auto Tune or Self Tune) control form must be P,
PI, PD or PID.
3 - If process set value is changed while Tune operation is being performed, Tune
operation is canceled.
i
3- After changing set value, if difference between newly defined set value and
former set value is greater than proportional band, device will start it.
If set value is changed to a value that is greater than;
± [ Scale * ( Heating or Cooling Proportional Band) ] /1000 value,
Parameter is adjusted by the device and Auto Tune operation is
started.
Example -1 : Starting Auto Tune operation by the user ;
! Enter technician menu.
! Adjust tune selection parameter in ”run List” menu , Auto Tune
Or Auto-Self Tune
! Adjust automatic tune selection parameter in ”run List” menu
And return to main operation screen.
! Observe that “AT” led is active.
Canceling Auto Tune operation
Auto Tune is canceled. Then, without doing any changes in PID parameters and
Parameter, device continues to run with former PID parameters.
:
1- If sensor breaks ;
2- If Auto Tune operation can not be completed in 8 hours
3- If user adjusts parameter or
4- If user adjusts parameter
5- If process set value is changed while Tune operation is being performed
6- While Tune operation is being performed, if operation type selection is changed
as “Manual” when it is “Automatic” (If operation type selection is changed as
“Automatic” when it is “Manual”, then Tune operation is started again)
7- If output function is changed while Tune operation is being performed
(HeatÞCool, CoolÞHeat)
8- While Tune operation is being performed, if control form is changed as “ON/OFF”
when it is “PID” (If control form is changed as “PID” when it is “ON/OFF”, the Tune
operation is started again)
If Auto Tune operation finishes without any problem, device saves the PID
coefficients to memory and continue to run. Parameter is adjusted
automatically.
There are 2 different methods for determining PID parameters by the device. These
are Auto tune ( Limit Cycle Tuning) and Self Tune (Step Response Tuning)
methods.
TUNE METHODS
Determining of PID parameters with Auto Tune is started in these conditions :
1- By the user in any time,
2- By the device when system gets unstable and starts oscillation
If process value is out of Set ± Process value stabilisation value (Please
refer to Section 6.2.4) and starts to oscillates, then device changes the
Parameter to and Auto Tune operation is started.