This parameter is added to the %process output that is calculated at
the end of the PID according to process set value.
* /(-)
If = 500°C , = 1000 , = 0 , = 5.0
* / ( - ) = 5.0 * 500 /(1000-0) = 2.5
2.5% is added to calculated process value.
Example: °C %
then %
86
(FOR HEATING PID 0.0 , 100.0 )
(FOR COOLING PID -100.0 , 0.0 )
(FOR HEATING-COOLING PID -100.0 , 100.0 )
%%
%%
%%
This parameter is added to “Output %” which is calculated at the end of
the PID.
500
PoFS = 5.0%