Cooling output can not be active less than this parameter. Even if this
parameter is 0, this parameter is accepted 50 msecs for security. While
motorized valve control is running if parameter is selected
heating or cooling, this parameter is not accessible.
84
OLLC
OUTPUT
PERIOD
GIVEN
OUTPUT
CALCULATED
OUTPUT
OULC
OUTPUT
PERIOD
GIVEN
OUTPUT
CALCULATED
OUTPUT
COOLING MINIMUM CONTROL OUTPUT ( 0.0 , )%
COOLING MAXIMUM CONTROL OUTPUT ( , 100.0 )%
COOLING MINIMUM CONTROL OUTPUT TIME (0.0 sec , )
It is % of cooling minimum output. If heating and cooling PID control
functions operate together, this parameter is not considered.
Even as a result of the cooling PID calculation device calculates the
output value less than this parameter, cooling output is active minimum
for OLLC parameter.
It is % of cooling maximum output.
Even as a result of the cooling PID calculation device calculates the
output value greater than this parameter, cooling output is active
maximum for OULC parameter.