4.2.2 EMO-410 SSR Driver Output Module
4.2.1 EMO-400 Relay Output Module
4.2 Output Modules
Specifications of EMO-400 Relay Output Module
Output
Dimensions
Electrical Life
: 3A@250V at resistive load, Single Open(or Close) Contact
: 14x30.7x41.4mm
: 100.000 Operation (Full Load)
V
EMO-400 Relay output module can be plugged in Module-1 or Module-2 socket to use functions
which are defined for relay output.
Applications of EMO-400 Relay Output Module
It can be used with heating or cooling functions as process control output, as alarm output by
programmable different alarm functions, as logic output to transfer some datas on the device to
the system. These alternatives are explained in parameters section as logic output function.
Detailed information about functions of EMO-400 Relay Output Module are
given in parameters section. For using these functions EMO-400 Relay Output
Module must be installed to Module-1 or Module-2 socket.
Specifications of EMO-410 SSR Driver Module
Output :
Dimensions :
Maximum 20 mA, 15-18V
14x30.7x41.4mm
Z ±10 , isolated%
EMO-410 SSR Driver Output Module can be plugged in Module-1 or Module-2 socket to use
functions which are defined for SSR driver output.
Applications of EMO-410 SSR Driver Output Module
It can be used with heating or cooling functions as process control output, as alarm output by
programmable different alarm functions, as logic output to transfer some datas on the device to
the system.
If short output period is needed in a system, using SSR Driver output module is
recommended. ( Relay must not be used for short output periods because of limited life of their
relay contact (open/close events))
Note 1 :
Detailed information about functions of EMO-410 SSR Driver Output Module
are given in parameters section. For using these functions EMO-410 SSR
Driver Output Module must be installed to Module-1 or Module-2 socket.