Instructions

Aln2 ConF: Alarm-2 Output Configuration Parameters
i
“Aln2 Conf” Menu is accessible if parameter in “PCnF
ConF” is
Alarm output
Sensor break alarm output
Manual /Automatic selection output
Output is active when the process value is out of the band which
is defined with minimum value of operating scale and
maximum value of operating scale
Determines logic output function for Alarm-2 Output.
Determines Alarm type for Alarm-2 Output.
Process high alarm.
Process low alarm.
Deviation high alarm.
Deviation low alarm.
Deviation band alarm.
Deviation range alarm.
It is active if logic output function of Alarm Output-2 is alarm output.
Active if logic output function of Alarm-2 Output is alarm output.
Alarm- 2 hysteresis value.
Alarm on delay time for Alarm Output-2.
It can be adjusted from 0 to 9999 seconds. It is active if logic output
function of Alarm Output-2 is alarm output.
Alarm off delay time for Alarm Output-2.
It can be adjusted from 0 to 9998 seconds. When the value is bigger
than 9998, is seen on the screen. It means alarm latching output
is selected. It is active if logic output function of Alarm Output-2 is
alarm output.
Alarm stabilisation time for Alarm Output-2.
It can be adjusted from 0 to 99 second. Logic output function of
Output2 if is selected as Alarm ,ALS2 parameter will be activated.
After the unit is power-on and Alarm Stabilisation Time is expired,
Alarm Output-2 becomes active when the alarm conditions realised in
Alt2 parameter.
14