Instructions

For details on parameters, refer to Section 6.2.1
i
6 - If user does not do anything for 120 seconds
while device is on technician menus, device
turns to operation screen.
5 - If tuning operation can not be completed in 8 hours, AT led starts to
blink.Blinking can be canceled by pressing Enter button.
65
PSET
°C
°F
VV
PO
AO1
AO2
A
AT ASET1 ASET2
M
SET
P
AT A/M
°C
°F
VV
PO
AO1
AO2
A
AT PSET ASET1 ASET2
M
SET
P
AT A/M
°C
°F
VV
PO
AO1
AO2
A
AT PSET ASET1 ASET2
M
SET
P
AT A/M
8. Specifications
Device Type : Process Controller
Housing&Mounting : 48mm x 48mm x 87.5mm 1/16 DIN 43700 plastic
housing for panel mounting. Panel cut-out is 46x46mm
Type-1Enclosure Mounting
Protection Class : NEMA 4X (IP65 at front, IP20 at rear).
Weight : Approximately 0.15 Kg.
Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
oooo
Storage/Operating Temperature : -40 C to +85 C / 0 C to +50 C
Storage/Operating Humidity : 90 % max. (None condensing)
Supply Voltage and Power : 100 - 240 VV (-15% / +10%) 50/60 Hz 6VA
24 VV (-15% / +10%) 50/60 Hz 6VA
24 VZ (-15% / +10%) 6W
Process Inputs : Universal input TC, RTD, Z Voltage/Current
Thermocouple Input Types : Selectable by parameters
L (DIN43710) ,
J ,K ,R ,S ,T ,B ,E ,N (IEC584.1)(ITS90) , C (ITS90)
Thermoresistance Input Types : PT 100 (IEC751) (ITS90)
Z Voltage Input Types : Selectable by parameters 0..50mV Z , 0..5V Z,
0..10V Z
Z Current Input Types : Selectable by parameters 0...20mA Z , 4...20mA Z
Installation : Fixed installation Category II
Over Voltage Category : II
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous