User manual

6
2.3 Panel Mounting and Removing
5. Changing and Saving Temperature and Humidity Set Value
5.1 Changing and Saving Humidity Set Value
Main Operating Screen
When SET button pressed ‘’S’’ led will
be active and temperature set value will
be displayed.
Temperature Set Value Screen
Temperature set value can
be changed with increment
and decrement buttons.
When SET button pressed
temperature set value can be saved.
Goes Humidity SET
value screen.
Temperature set value parameter ( Default =50 )
Temperature set value, can be programmed between minimum temperature set value and
maximum temperature set value .
°C
When SET button pressed
set value can be saved.
Humidity
Goes back to main operation screen.
Main Operating Screen
Humidity Set Value Screen
If no operation is performed in Humidity set value changing mode and temperature set value
changing mode for 20 seconds, device turns to main operation screen automatically.
i
Humidity Set Value Screen
5.1 Programming Mode Parameter List
In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude
around set value changes according to
controlled system. For reducing oscillation
period of temperature value, a threshold
zone is formed below or around set value
and this zone is named hysteresis.
Temperature Sensor Offset Parameter ( Default = 0 )
3.2 Device Label and Connection Diagram
3. Electrical Wiring Diagram
3.1 Supply Voltage Input Connection of the Device
4.Front Panel Definition and Accessing to the Menus
5
7 8
11
9 10
12
Decimal Seperator Enabling Parameter ( Default = 0 )
None.
Only Temperature parameters with decimal seperator.
BUTTON DEFINITIONS
1. Increment Button :
** In main operation screen, press this button to change display temperature and humidity sensor
value.
** It is used to increase the value in the Temperature and Humidity Set screens and Programming mode.
2. Decrement, Silencing Buzzer Button :
** It is used to decrease the value in the Set screen and Programming mode.
** It is used to silence the buzzer.
3. Set Button:
** In the main operation screen; if this button pressed for the first time, Temperature set value will be
displayed. Value can be changed using increment and decrement buttons. When Enter button is
pressed again, value is saved and Humidty set value will be displayed next. Value can be changed using
increment and decrement buttons. When Enter button pressed again, value is saved and returns back
to main operating screen.
4.Enter Button:
** To access the programming screen; in the main operation screen, press and hold this button for 5
seconds.
** It is used to save value in the Set screens (Temperature or Humidity) and programming screen.
5.A1 led :
**
6. O1 Led :
** This led indicates that heating output is active.
7.Celcius led :
o
** Indicates that device is in C mode.
8.Fahrenheit led :
o
** Indicates that device is in F mode.
9. O2 Led :
** This led indicates that output is active.
10.A2 Led :
** This led indicates that Alarm is active.
11.Precent Sign ledi :
output is active
12.Program led :
** Indicates that device is in programming mode .
LED DEFINITIONS
It is active when Temperature alarm statuses.
Humidifier
Humidifier
** Indicates that device is in Humidity Set screen or Humidifier .
Temperature Unit Selection Parameter ( Default = 0 )
°C selected.
°F selected.
230VV CONNECTION DIAGRAM
Only Humidity parameters with decimal seperator.
Only Temperature and Humidity parameters with decimal seperator.
Temperature Control Selection Parameter On/Off or PID ( Default = 0 )
On - Off selected.
PID selected.
PID - Proportional Control Parameter ( Default =50 )
This parameter value can be adjusted form 0 to 100.
PID - Integral Parameter( Default = 1000 )
This parameter value can be adjusted form 0 to 3600.
PID - Derivative Parameter ( Default = 250 )
This parameter value can be adjusted form 0 to 3600.
PID -Period Time Parameter ( Default = 1 )
This parameter value can be adjusted form 1 to 50 second.
Humidity Sensor Scale Selection Parameter ( Default = 0 )
Buzzer Function Selection Parameter( Default = 0 )
Button Protection Parameter ( Default = 0 )
Programming Mode Accessing Password
It is used for accessing to programming mode. It can be adjusted from 0 to 9999. If it is 0,
password is not entered for accessing to the parameters. When the password screen is not
set as “12” , If the user enters ‘12’ in password screen and parameters are
accessed and they can changed.
( Default = 0 )
Humidity Alarm Function Selection Parameter ( Default = 0 )
Humidity (Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
Humidity alarm.
Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
Humidity Set Maximum Parameter(Default =Maximum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from humidity alarm set
minimum parameter to maximum value of the device scale.
Alarm
Humidity (Default = 0)
Humidity
Alarm On Delay Time Parameter
Alarm On Delay Time can be defined with this parameter. It can be adjusted
from 0 to 99 minutes.
Buzzer is inactive.
Buzzer is active during temperature alarm
Buzzer is active during humidity alarm
Buzzer is active during Temperature sensor failures.
Buzzer is active during Humidity sensor failures.
Buzzer is active during Temperature sensor failures or temperature alarm.
Buzzer is active during Humidity sensor failures or Humidity alarm.
Buzzer is active during Temperature sensor failures or Humidity sensor failures
Buzzer is active during Temperature sensor failures or Humidity sensor failures
or temperature alarm or humidity alarm.
There is no protection.
Temperature set value can not be changed.
Humidity set value can not be changed.
Temperature set value and Humidity set value can not be changed
Nem Set Parametresi (Default = 60%)
Humidity set value, can be programmed between minimum Humidity set value and maximum
temperature set value .
1-Before mounting the device in your panel, make
sure that the cut-out is of the right size.
2-Insert the device through the cut-out. If the
mounting clamps are on the unit, put out them
before inserting the unit to the panel.
3- Insert the mounting clamps to the fixing sockets
that located left and right sides of device and
make the unit completely immobile within the
panel
1-Pull mounting clamps from left and right
fixing sockets.
2-Pull the unit through the front side of the
panel
Before starting to remove the unit
from panel, power off the unit and
the related system.
c
Make sure that the power supply voltage is the same indicated on
the instrument.
Switch on the power supply only after that all the electrical
connections have been completed.
Supply voltage range must be determined in order. While installing
the unit, supply voltage range must be controlled and appropriate
supply voltage must be applied to the unit.
c
There is no power supply switch on the device. So a power supply
switch must be added to the supply voltage input.
Power switch must be two poled for seperating phase and neutral,
On/Off condition of power supply switch is very important in
electrical connection.
External fuse that on Vpower supply inputs must be on phase
connection.
External fuse that on Z power supply inputs must be on (+)
connection.
c
Power Supply Input
c
a
External
Fuse
(1A T)
Note-1
Supply
Switch
7
8
L
N
Supply Voltage
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz ,
24V ( %15)50/60Hz ,
24V ( %15) 50/60Hz ,
Z
V ±
V ±
V ±
W ±
10...30 V 1.5 W
Must be determined in order.
ON
OFF
Temperature
Control
Output
Set
thSt
Time
thSt
Time
Temperature Set Value Screen
Humidity Set Value Screen
Humidity set value can be
changed with increment
and decrement buttons.
Relay Outputs
2
1
3 54 6 87 9 10
P/N : ESM-3723
L
N
aa
Power Supply Voltage
230V ( %15) 50/60Hz ,
115V ( %15) 50/60Hz,
24V ( %15) 50/60Hz ,
24V ( %15) 50/60Hz ,
Z
V ±
V ±
V ±
W ±
10...30 V 1.5 W
11 12
Temperature Sensor Input
NTC, PTC, PT-100, 0/2..10V, 0/4..20mA
or ProNem Mini PMI-P
Humidity Sensor Input
0/2..10V, 0/4..20mA or
ProNem Mini PMI-P
Must be determined in order.
3
2
1
1
2
Must be determined in order.
Must be determined in order.
N
L
7
8
9
10
a
3x3A@ 250V V
5A @250VV
L
N
230 VV ± 15%
50/60Hz - 1.5VA
2
3
41
5
6 11 12
14A T Fuse
+
-
N
L
7
8
9
10
a
3x3A@ 250V V
5A @250VV
L
N
230 VV ± 15%
50/60Hz - 1.5VA
2
3
41
5
6 11 12
14A T Fuse
+
-
PTC Temperature and 0/4..20mA Humidity Sensor Input connection
VCC
GND
SCL
SDA
ProNem Mini PMI-P Temperature and Humidity Sensor Input Connection
Note: If this parameter is select 0, PID parameters ( , , , , ) will be not observed.
If this parameter select 1, parameter will be not observed.
Auto Tune (Limit Cycle Tuning) Selection Parameter ( Default = )
Device does not do(Limit cycle Tuning) operation.
Device does operation.
Hysteresis Parameter for Temperature ( Default = 0.1 °C )
From 1 to 10°C for NTC,PTC, PT-100 (0°C, 100°C)
From 1 to 18°F for NTC,PTC ,PT-100 (32°F, 212°F)
From 0.1 to 10.0°C for NTC, PTC, PT-100 (0.0°C,100.0°C)
From 0.1 to 18.0°F for NTC, PTC, PT-100 (32.0°F,212.0°F)
From 1 to 10°C for ProNem Mini PMI-P (-20°C, 80°C) ,From 1 to 18°F for ProNem Mini
PMI-P (-4°F,176°F),From 0.1 to 10.0°C for ProNem Mini PMI-P (-20.0°C,80.0°C)
From 0.1 to 18.0°F for ProNem Mini PMI-P (-4.0°F,176.0°F).
Minimum Temperature Set Value Parameter ( Default = 10.0°C)
Temperature set value can not be lower than this value. This parameter value can be
adjusted from minimum value of device scale to maximum temperature set value
parameter
Maximum Temperature Set Value Parameter ( Default = 40.0 °C )
Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale.
From -10 to 10°C , NTC,PTC , PT-100 (0°C, 100°C)
From -18 to 18°F, NTC,PTC , PT-100 (32°F, 212°F)
From -10.0 to 10.0°C , NTC ,PTC , PT-100 (0.0°C,100.0°C)
From -18.0 to18.0°F NTC, PTC , PT-100 (32.0°F,212.0°F)
From -10 to 10°C ,ProNem Mini PMI-P ( -20°C, 80°C ),From -18 to 18°F,ProNem Mini PMI-
P ( -4°F, 176°F ),From -10.0 to 10.0°C, ProNem Mini PMI-P ( -20.0°C, 80.0°C ),
From -18.0 to18.0°F, ProNem Mini PMI-P ( -4.0°F,176.0°F )
0..10V 0..20mA Z or Z
2..10V 4..20mA Z or Z
(1) (2)
(2)(1)
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z Humidity Sensor Input.
Z Humidity Sensor Input .
(1)
(2)
i
Humidity input range is determined with this parameter.
Note : parameter ProNem Mini PMI-P type device are not observed.
Hysteresis Parameter for Humidity ( Default = 1 )
From 1 to 10 for Humidity Sensor (0%RH, 100%RH)
From 0.1to 10.0 for Humidity Sensor (0.0%RH,100.0%RH)
In ON/OFF control algorithm,
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude
around set value changes according to
controlled system. For reducing oscillation
period of temperature value, a threshold
zone is formed below or around set value
and this zone is named hysteresis.
Humidity
ON
OFF
Humidity
Control
Output
Set
hhSt
Time
hhSt
Time
Maximum Humidity Set Value Parameter (Default = Maximum Value of Device Scale)
This parameter value can be
adjusted from minimum humidity set value parameter to maximum value of the
device scale.
Humidity set value can not be greater than this value.
Minimum Humidity Set Value Parameter (Default = Minimum Value of Device Scale)
set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum set value parameter
Humidity
Humidity
Humidity Sensor Offset Parameter ( Default = 0.0 )
From -10 to 10%RH for (0%RH-100%RH)
From -10.0 to 10.0%RH for (0.0%RH-100.0%RH)
Humidity Sensor
Humidity Sensor
Temperature Alarm is inactive.
Temperature Alarm Set Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum parameter.
( Default = 50.0 °C )
Temperature Alarm Function Selection Parameter ( Default = 0 )
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Alarm Set Maximum Parameter ( Default = Maximum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from temperature
alarm set value parameter to maximum value of the device scale.
Alarm Set Minimum Parameter (Default = Minimum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from minimum value of
device scale to temperature alarm set maximum parameter value.
Temperature Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
( Default = 0)
Temperature Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
( Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Humidity Alarm Set Parameter
This parameter value can be programmed between humidity minimum alarm set
parameter and humidity alarm set maximum parameter.
( Default = 60 )
Humidity Set Minimum Parameter(Default =Minimum Value of Device Scale)
if humidity alarm is active, this parameter value can be adjusted from minimum value of
device scale to humidty alarm set maximum parameter value.
Alarm
Humidity Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Buzzer Active Time
If buzzer function selection parameter
Buzzer active time can be define with this parameter. It can be adjusted from 1 to 99
minutes. When this parameter is 1, if decrement button is pressed, is observed. In
this condition buzzer is active till buzzer silence button is pressed.
( Default = )
value = 0, this parameter is not observed.
Note-1: External Fuse is recommended
WHITE
YELLOW
BROWN
GREEN
ProNem Mini
PMI-P
BLACK
Shield
3
4
1
2
5
6
9
10
7
8
11
12
ESM-3723
ü
SET
P
O1
O2
A1
A2
O
C
O
F
O1
ESM-3723
ü
SET
O1
ESM-3723
ü
SET
ESM-3723
SET
ü
ESM-3723
SET
ü
ESM-3723
SET
ü
ESM-3723
SET
ü
ESM-3723
SET
ü
HEAT.
ALARM
HUM.
HUM.
ALARM/
HEAT
230 VV ± 15%
50/60Hz - 1.5VA
230 VV ± 15%
50/60Hz - 1.5VA
HEAT
ALARM
HUM.
HEAT
HUM.
ALARM/
Humidity Alarm is inactive.
Note : If this parameter is select 0, Temperature Alarm parameters , , , , and
will be not observed.
Note : If this parameter is select 0, Humidity Alarm parameters , , , , and
will be not observed.
Note : When value of or parameters are changed , the values of , , , ,
, , , , , , , , , , , , and parameters
should be changed accordingly.
Note : Shield (Black) pin must be connected to number 10 (GND) of the terminal block.
P/N : ESM-3723 - 5.6.6.0.1/01.01/1.6.6.0
P/N : ESM-3723-5.2.5.0.1/01.01/1.2.0.0
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z Sensor Input.
Z Sensor Input
Temperature
Temperature .
(1)
(2)
i
0..10V veya 0..20mA Z Z
2..10V veya 4..20mA Z Z
Temperature Sensor Scale Selection Parameter ( Default = 0 )
(1) (2)
(2)(1)
Analogue (T input range is determined with this parameter.emperature)
Temperature
or
or
Sensor Scale Low Limit Parameter : ( Default = 0 )
It can be adjusted from -1999 to ( -1). At this value analogue input becomes;
If =0, according to the device type 0V 0mA
If =1, according to the device type 2V 4mA
ZZ
ZZ
(1) (2)
(1) (2)
Temperature
or
Sensor Scale High Limit Parameter : ( Default = 100 )
It can be adjusted from ( +1) to 9999. At this value analogue input becomes;
According to the device type 10V 20mA ZZ
(1) (2)
Note : , parameters are shown, if the Temperature sensor analogue input type is selected .
Note : , and parameters are shown, if the Temperature sensor analogue input type
( 0/2..10V or 0/4..20mA ) is selected.