User manual
2.2 Panel Cut- Out
ESM-3723 77x35 DIN Size Temperature+Humidity
Instruction Manual. ENG ESM-3723 01 V03 02/15
2. General Description
2.1 Front View and Dimensions of ESM-3723 Temperature Controller
All order information of ESM-3723 Temperature+Humidity Controller are given on the table at above.
User may form appropriate device configuration from information and codes that at the table and
convert it to the ordering codes.Firstly, supply voltage then other specifications must be determined.
Please fill the order code blanks according to your needs. Please contact us, if your needs are out of the
8. Other Informations
When SET button is pressed for 3
seconds, “P” led turn. If programming
mode entering password is different
from 0, programming mode entering
screen will be observed.
Main Operation Screen
Programming Screen
Change the value with increment
and decrement buttons.
Press SET button for accessing to the
parameter value. Press increment
button for accessing to the next
parameter, press decrement button for
accessing to the previous parameter.
Press set button for saving the
parameter.
Press increment button for accessing to
the next parameter, press decrement
button for accessing to the previous
parameter.
Programming Mode
Entering Screen
Press SET button for
accessing to the
password entering
Password Entering Screen
Enter programming mode accessing
password with increment and
decrement buttons.
Note2: If programming mode accessing password is 0, only three parameters are accessible, and the
parameter values can be changed.
Press SET/OK button for
entering the password.
Note1: If programming
mode accessing password
is 0, Temperature Unit
screen is observed
instead of programming
screen
If no operation is performed in programming mode for 20 seconds, device turns to main
operation screen automatically.
i
Decimal Separator Enabling
Selection Screen
5.5 Entering To The Programming Mode, Changing and Saving Parameter
14
13
76 mm / 3 inch
34,5 mm / 1.36 inch
15
Note-1: If input type is selected PTC or NTC (BC= 2, 3), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0, 3 or 4) must be declared in ordering information.
7. Specifications
Password Entering Screen
Temperature Unit Selection
Parameter Value
Temperature Unit Selection
Parameter Value
7. Specifications
c
1.2. General Specifications
1.Preface
ESM-3723 series Temperature + Humidity control devices, are designed for the control of industrial
processes. PID or On / Off control form under the control of the process is a device that can
respond to your special needs.
ESM-3723
Power Supply
Input
Output
Output
Output
2
Heating Alarm
Humidifier
Humidifier Alarm
1.1 Environmental Ratings
- 4 Digits for Temperature Display
- 4 Digits for Humidity Display
- Temperature Sensor Input
NTC, PTC, PT-100, 0/2..10V, 0/4..20mA or ProNem Mini PMI-P
(Must be determined in order.)
- Humidity Sensor Input
0/2..10V, 0/4..20mA or ProNem Mini PMI-P
(Must be determined in order.)
- 4 Output
Heating Control Output
Heating Alarm Output
Humidification Control Output
Humidification Alarm Output
- Relay or SSR Outputs (Must be determined in order.)
- Selectable Temparature Control ( PID or ON / OFF )
- Auto-Tune PID
- Set value boundaries
- Alarm parametreters
- Adjustable internal buzzer according to the alarm situations
- Password protection for programming mode,
- Having CE mark according to European Norms
ESM-3723 77 x 35 DIN Size
Digital Temperature+Humidity Controller
3 416
Mounting Clamp
Panel Surface
(maximum thickness 15 mm / 0.59 inch)
Front panel
IP65 Protection
NEMA 4X
65 mm / 2.56 inch
6 mm / 0.24 inch
110 mm / 4.33 inch (min)
71 mm / 2.79 inch
29 mm / 1.14 inch
50 mm / 1.97 inch (min)
Maximum 15 mm / 0.59 inch
230V ( %15)50/60HzV ±
Optional Supply
Voltage
- 30 V Z
115 V (±%15)50/60Hz
24 V (±%15)50/60Hz
24 V (±%15)50/60Hz
10
V
V
W
Standard
Device Type : Temperature+Humidity Controller
Housing&Mounting : 76 mm x 34.5 mm x71 mm Plastic housing for panel
Panel cut out is 71 x 29 mm.
Protection Clas : Ip65 at front, Ip20 at rear.
Weight : Approximately 0.2 Kg
Enviromental Ratings : Standart,indoor at an altitude of less than 2000 meters with
none condensing humidity.
oooo
Storage / Operating Temperature : -40 C to +80 C / -30 C to +80 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
: 115
: 24
: 24
: 10-30
Temperature Sensor Input : NTC, PTC, PT-100,0/2..10VZ,0/4..20mAZ or
ProNem Mini PMI-P
NTC input type : NTC (10 kW @25 °C )
230V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
VZ 1.5W
V ±
V ±
V ±
W ±
Output
Heating
Your Technology Partner
www.emkoelektronik.com.tr
Thank you very much for your preference to
use Emko Elektronik products, please visit our
web page to download detailed user manual.
Operating Temperature : 0 to 50 °C
Max. Operating Humidity : 90% Rh (non-condensing)
Altitude : Up to 2000 m.
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
A visual inspection of this product for possible damage occurred during shipment is recommended
before installation.
It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the system
and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse as
required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent failure
Keep the power off until all of the wiring is completed so that electric shock and trouble with the unit can
be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal burrs can
cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage of the
device with inappropriate fixing clamp. Be sure that device will not fall while doing the montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts from the
delivery date. This warranty is in force if duty and responsibilities which are determined in warranty
document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the device before
accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of these
solvents can reduce the mechanical reliability of the device. Use a cloth dampened in ethyl alcohol or
water to clean the external plastic case.
1.3 Installation
1.4 Warranty
1.5 Maintenance
1.6 Manufacturer Company
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Þ.
Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Repair and maintenance service information:
Emko Elektronik Sanayi ve Ticaret A.Þ.
Demirtaþ Organize Sanayi Bölgesi Karanfil Sk. No:6 16369 BURSA/TURKEY
Phone : +90 224 261 1900
Fax : +90 224 261 1912
Temperature Sensor
Input
Humidity Sensor Input
5.2 Alarm Output Graphics of ESM-3723
i
Process High Alarm
ON
OFF
Alarm
Output
Process Value
Process Low Alarm
ON
OFF
Alarm
Output
Process Value
Deviation Band Alarm
ON
OFF
Alarm
Output
( - Alarm Set)
= Process Set Value (Temperature or Humidity)
Deviation Range Alarm
ON
OFF
Alarm
Output
Process Value
Alarm Set
Alarm Set
( +Alarm Set)
( - Alarm Set) ( +Alarm Set)
Process Value
1- Screen Blinking Temperature Sensor failure . Sensor connection is wrong or there is no sensor
connection. While this message shown on this display,if buzzer function selection is 3, 5, 7 or 8
internal buzzer starts to operate.
5.3 Failure Messages in ESM 3723
2- Screen Blinking H Sensor failure . Sensor connection is wrong or there is no sensor
connection. While this message shown on this display,if buzzer function selection is 4, 6,7 or 8
internal buzzer starts to operate.
umidity
PTC input type : PTC (1000 W @25 °C )
Termoresistance input type : PT-100 IEC751 (ITS90 )
Humidity input type : 0/2..10VZ,0/4..20mAZ or ProNem Mini PMI-P
Accuracy : ± 1 % of full scale
Sensor Break Protection : Upscale
Control Form : PID or ON / OFF
Relay Outputs : 5 A@250 V V at Resistive Load (Heating Output)
: 3 A@250 V V at Resistive Load ((Heating , (Heating
Alarm), (Humidifier ), (Humidifier Alarm ))
Optional SSR Driver Output : Maximum 30mA, Maximum 15V
Temperature Display : 8 mm Red 4 digit LED Display
Humidity Display : 8 mm Green 4 digit LED Display
oo
LED Displays : P (Green), % (Green), C (Red), F(Red),
Humidifier Output (Red), Humidifier Alarm Output (Red)
Heating Output (Red), Heating Alarm (Red)
Internal Buzzer : ³83dB
Upprovals : ,
6. Auto Tune Metod
Starting Auto Tune (Limit Cycle Tuning)
Operation by the user :
• Adjust t
• Adjust auto tune selection parameter ( = )
• In the main screen “Atun” and Temperature value
are should alternately.
emperature control on/off or PID parameter
( =1)
Auto Tune method is used for determining PID parameters used by the device.
If Auto Tune operation is finished without any problem,
the device saves the new PID coefficients, calculated
using the previously found “T” and “B” values, to
memory and continue to run.
parameter is adjusted automatically.
Temperature
Value
Time
Heating
Output
Time
B
T
Cancelling Auto Tune (Limit Cycle Tuning) operation :
1 - If sensor breaks;
2 - If auto tune operation can not be completed in 8 hours ;
3 - If user adjusts parameter ;
4- During auto tune operation if the user changes the temperature control from pid to on/off;
5 - If process set value is changed while auto tune operation is being performed;
Auto tune is canceled. “Atun” is not displayed. Then, without doing any changes in PID
parameters, device continues to run with previous PID parameters.
ESM-3723
ü
SET
P
O1
O2
A1
A2
O
C
O
F
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
ESM-3723
SET
ü
O1
3- In main operating screen if the upper display is blinking, it means that temperature alarm exits and
alarm output is active .if buzzer function selection is 1, 5 or 8 internal buzzer starts to operate.
4- In main operating screen if the lower display is blinking, it means that humidity alarm exits and alarm
output is active .if buzzer function selection is 2, 6 or 8 internal buzzer starts to operate.
B C D E FG HI /
/
U
V W Z/
/
0
Power Supply VoltageA
Temperature Sensor Input
B
Scale(°C/°F)
ESM-3723 (77x35 DIN Size)
4
-20°C/-4°F ; 80°C/176°F
115V ( %15) 50/60Hz - 1.5VAV ±
ProNem Mini PMI-P
PT 100, IEC751(ITS90)
1
PTC (Not-1)
2
5
230V ( %15) 50/60Hz - 1.5VAV ±
8
10 - 30 V Z 1.5W
0°C/32°F ;100°C/212°F
0°C/32°F ;100°C/212°F
NTC (Not-1)
3
0°C/32°F ;100°C/212°F
3
24V ( %15) 50/60Hz - 1.5VAV ±
0
2
24V ( %15) 50/60Hz - 1.5VAW ±
0% - 100%
0% - 100%
0% - 100%
0/2..10Vdc Voltage Input
4
5
0/4..20mA Current Input
6
Humidity Sensor Input
C
Scale (%)
ProNem Mini PMI-P
0/2..10Vdc Voltage Input
4
5
0/4..20mA Current Input
6
01
Relay Output ( 3A@250 V V,at Resistive Load ,1 NO )
Humidifier Output
FG
1
Relay Output ( 5 A@250 V V,at Resistive Load 1NC ,1 NO )
Heating Output
E
2
SSR Drive Output ( Maximum 30mA,Maximum 15V )
01
Relay Output ( 3A@250 V V,at Resistive Load ,1 NO )
Heating Alarm Output
HI
1
Relay Output ( 3A@250 V V,at Resistive Load ,1 NO )
Humidifier Alarm Output
U
Temp.Sensor which is given with ESM-3723
V
0
None
3
NTC-M5L20.K1.5 (NTC Probe thermoplastic moulded with
1.5m cable for cooling application)
4
NTC-M6L50.K1.5 (NTC Probe stainless steel housing with
1.5m cable for cooling application)
9
ProNem Mini PMI-P (2.5m cable for Temperature and Humidity
application)
6
Customer
1
PTC-M6L40.K1.5 (PTC Air Probe 1.5 m silicon cable)
2
PTCS-M6L30.K1.5.1/8”(PTC Liquid Probe with 1.5 m silicon cable)
A
PTC, NTC, PT-100
0/2..10V,0/4..20mA or
ProNem Mini PMI-P
0/2..10V,0/4..20mA or
ProNem Mini PMI-P
User defined
User defined