5.1 Programming Mode Parameter List
9
Decimal Seperator Enabling Parameter ( Default = 0 )
None.
Only Temperature parameters with decimal seperator.
Temperature Unit Selection Parameter ( Default = 0 )
°C selected.
°F selected.
Only Humidity parameters with decimal seperator.
Only Temperature and Humidity parameters with decimal seperator.
Temperature Control Selection Parameter On/Off or PID ( Default = 0 )
On - Off selected.
PID selected.
PID -Period Time Parameter ( Default = 1 )
This parameter value can be adjusted form 1 to 50 second.
Note: If this parameter is select 0, PID parameters ( , , , , ) will be not observed.
If this parameter select 1, parameter will be not observed.
Note : When value of or parameters are changed , the values of , , , ,
, , , , , , , , , , , , and parameters
should be changed accordingly.
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z Sensor Input.
Z
Sensor Input
Temperature
Temperature
.
(1)
(2)
i
0..10V veya 0..20mA
Z Z
2..10V veya 4..20mA Z Z
Temperature Sensor Scale Selection Parameter ( Default = 0 )
(1) (2)
(2)(1)
Analogue (T input range is determined with this parameter.emperature)
Temperature
or
or
Sensor Scale Low Limit Parameter : ( Default = 0 )
It can be adjusted from -1999 to ( -1). At this value analogue input becomes;
If =0, according to the device type 0V
0mA
If =1, according to the device type 2V
4mA
Z Z
Z Z
(1) (2)
(1) (2)
Temperature
or
Sensor Scale High Limit Parameter : ( Default = 100 )
It can be adjusted from ( +1) to 9999. At this value analogue input becomes;
According to the device type10V
20mA
Z
Z
(1)
(2)
Note : , parameters are shown, if the Temperature sensor analogue input type is selected .
Note : , and parameters are shown, if the Temperature sensor input type
( 0/2..10V or 0/4..20mA ) is selected.
analogue
PID - Proportional Control Parameter ( Default =1.0 )
This parameter value can be adjusted form 0.0 to 100.0
PID - Integral Parameter( Default = 300 )
This parameter value can be adjusted form 0 to 3600.
PID - Derivative Parameter ( Default = 60 )
This parameter value can be adjusted form 0 to 999.9
Self Tune Selection Parameter ( Default = )
Device does not do operation.
Device does operation.