Instructions

15
7. Specifications
Device Type : Temperature+Humidity Controller
Housing&Mounting : 76 mm x 34.5 mm x71 mm Plastic housing for panel
Panel cut out is 71 x 29 mm.
Protection Clas : Ip65 at front, Ip20 at rear.
Weight : Approximately 0.2 Kg
Enviromental Ratings : Standart,indoor at an altitude of less than 2000 meters with
none condensing humidity.
o
o
o
o
Storage / Operating Temperature : -30 C to +80 C / -20 C to +70 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
: 115
: 24
: 24
: 10-30
Temperature Sensor Input : NTC, PTC, PT-100,0/2..10VZ,0/4..20mAZ or
ProNem Mini PMI-P
NTC input type : NTC (10 kW @25 °C )
230V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
VZ 1.5W
V ±
V ±
V ±
W ±
6. Self Tune Metod
Starting Self Tune (Step Response Tuning) Operation by the user :
Self Tune method is used for determining PID parameters used by the device.
If Self Tune operation is finished without any problem, the device saves the new PID coefficients to
memory and continue to run. Parameter is adjusted automatically.
NOT: The temperature value read from the sensor must be less than 5% of the process set value in order
to start the self tune operation (5 ° C for the ProNem Mini PMI-P sensor).
Cancelling Self Tune(Step Response Tuning) operation :
1 - If sensor breaks;
2 - If auto tune operation can not be completed in 8 hours ;
3 - If user adjusts parameter ;
4- During self tune operation if the user changes the temperature control from pid to on/off;
5 - If process set value is changed while self tune operation is being performed;
Self tune is canceled. “Tune” is not displayed. Then, without doing any changes in PID parameters,
device continues to run with previous PID parameters.
Adjust t
Adjust self tune selection parameter ( = )
In the main screen “Tune” and Temperature value are should alternately.
emperature control on/off or PID parameter
( =1)