Instructions

11
Humidity Alarm Function Selection Parameter ( Default = 0 )
Maximum Humidity Set Value Parameter (Default = Maximum Value of Device Scale)
This parameter value can be
adjusted from minimum humidity set value parameter to maximum value of the
device scale.
Humidity set value can not be greater than this value.
Minimum Humidity Set Value Parameter (Default = Minimum Value of Device Scale)
set value can not be lower than this value. This parameter value can be adjusted
from minimum value of device scale to maximum set value parameter
Humidity
Humidity
Humidity Sensor Offset Parameter ( Default = 0.0 )
From -10 to 10%RH for Humidity Sensor (0%RH-100%RH)
From -10.0 to 10.0%RH for Humidity Sensor (0.0%RH-100.0%RH)
Temperature Alarm is inactive.
Temperature Alarm Set Parameter
This parameter value can be programmed between temperature minimum alarm set
parameter and temperature alarm set maximum parameter.
( Default = 50.0 °C )
Temperature Alarm Function Selection Parameter ( Default = 0 )
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Alarm Set Maximum Parameter ( Default = Maximum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from temperature
alarm set value parameter to maximum value of the device scale.
Alarm Set Minimum Parameter (Default = Minimum Value of Device Scale)
if temperature alarm is active, this parameter value can be adjusted from minimum value of
device scale to temperature alarm set maximum parameter value.
Temperature Alarm Parameter
This parameter value can be adjusted form 0 to %50 of the device scale.
Hysteresis ( Default = 0)
Temperature Alarm On Delay Time Parameter
Temperature Alarm On Delay Time can be defined with this parameter. It can be
adjusted from 0 to 99 minutes.
( Default = 0)
Temperature Alarm Delay After Power On Parameter
It can be adjusted from 0 to 99 minutes.
( Default = 0)
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm.
Process High alarm selected.
Process Low alarm selected.
Deviation Band alarm selected.
Deviation Range alarm selected.
Humidity Alarm is inactive.
Note : If this parameter is select 0, Temperature Alarm parameters , , , , and
will be not observed.
Note : If this parameter is select 0, Humidity Alarm parameters , , , , and
will be not observed.