Instructions

In ON/OFF control algorithm, temperature
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude
around set value changes according to
controlled system. For reducing oscillation
period of temperature value, a threshold
zone is formed below or around set value
and this zone is named hysteresis.
Temperature Sensor Offset Parameter ( Default = 0 )
10
Humidity Sensor Scale Selection Parameter ( Default = 0 )
ON
OFF
Temperature
Control
Output
Set
thSt
Time
thSt
Time
Hysteresis Parameter for Temperature ( Default = 0.1 °C )
From 1 to 10°C for NTC,PTC, PT-100 (0°C, 100°C)
From 1 to 18°F for NTC,PTC ,PT-100 (32°F, 212°F)
From 0.1 to 10.0°C for NTC, PTC, PT-100 (0.0°C,100.0°C)
From 0.1 to 18.0°F for NTC, PTC, PT-100 (32.0°F,212.0°F)
From 1 to 10°C for ProNem Mini PMI-P (-20°C, 80°C) ,From 1 to 18°F for ProNem Mini
PMI-P (-4°F,176°F),From 0.1 to 10.0°C for ProNem Mini PMI-P (-20.0°C,80.0°C)
From 0.1 to 18.0°F for ProNem Mini PMI-P (-4.0°F,176.0°F).
Minimum Temperature Set Value Parameter ( Minimum Value of Device)
Temperature set value can not be lower than this value. This parameter value can be
adjusted from minimum value of device scale to maximum temperature set value
parameter
Maximum Temperature Set Value Parameter ( Maximum Value of Device )
Temperature set value can not be greater than this value.
This parameter value can be adjusted from minimum temperature set value parameter
to maximum value of the device scale.
From -10 to 10°C , NTC,PTC , PT-100 (0°C, 100°C)
From -18 to 18°F, NTC,PTC , PT-100 (32°F, 212°F)
From -10.0 to 10.0°C , NTC ,PTC , PT-100 (0.0°C,100.0°C)
From -18.0 to18.0°F NTC, PTC , PT-100 (32.0°F,212.0°F)
From -10 to 10°C ,ProNem Mini PMI-P ( -20°C, 80°C ),From -18 to 18°F,ProNem Mini
PMI-P ( -4°F, 176°F ),From -10.0 to 10.0°C, ProNem Mini PMI-P ( -20.0°C, 80.0°C ),
From -18.0 to18.0°F, ProNem Mini PMI-P ( -4.0°F,176.0°F )
0..10V 0..20mA Z or Z
2..10V 4..20mA Z or Z
(1) (2)
(2)(1)
It is valid, if the device type 0/2...10V
It is valid, if the device type 0/4...20mA
Z Humidity Sensor Input.
Z Humidity Sensor Input .
(1)
(2)
i
Humidity input range is determined with this parameter.
Note : parameter ProNem Mini PMI- type device are not observed.P
Hysteresis Parameter for Humidity ( Default = 1 )
From 1 to 10 for Humidity Sensor (0%RH, 100%RH)
From 0.1to 10.0 for Humidity Sensor (0.0%RH,100.0%RH)
In ON/OFF control algorithm,
value is tried to keep equal to set value by
opening or closing the last control element.
ON/OFF controlled system, temperature
value oscillates continuously. Temperature
value’s oscillation period or amplitude
around set value changes according to
controlled system. For reducing oscillation
period of temperature value, a threshold
zone is formed below or around set value
and this zone is named hysteresis.
Humidity
ON
OFF
Humidity
Control
Output
Set
hhSt
Time
hhSt
Time