6.3 Modbus Adresses of Device Status Parameters (Read Input Register)
11
Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40023
Buzzer is inactive.
Buzzer is active if an alarm occurs.
Buzzer is active during this time
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40024
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
Programming Section Accessing Password 28
.
( Default = 0 ) MODBUS ADDRESS:400
It is used for accessing to the programming section. It can be adjusted from 0 to 9999. If it is
selected 0, password will not be asked
PROKEY communication selected.
Communication Mode Selection Parameter 25( Default = 0 ) MODBUS ADDRESS:400
RS 485 communication selected.
Slave ID Parameter 26( Default = 1 ) MODBUS ADDRESS=400
Device communication address parameter (1 to 247).
Buzzer is active during sensor failures.
Buzzer is active during alarm or sensor failures.
, , , , and Parameters are observed if Operation type
is selected “Cooling”. If operation type is selected “Heating ” ,skip to the parameter.
i
MODBUS ADRES:30001 Temperature Value
o
MODBUS ADRES:30002 Led Status : 0.bit C Led,6.bit Compressor Led,
7.bit Alarm Led, 13.bit Program Led,
14.bit Set Led
MODBUS ADRES:30003 Device Status : 0.bit Alarm Status
2.bit Buzzer Status
3.bit Sensor Break Status
MODBUS ADRES:30004 Output Status 0.Bit Compressor Output,1.bit Alarm Output
MODBUS ADRES:30005 Device Type and Device Version
A
Manual Alarm Output Active Parameters (Default=0) MODBUS ADDRESS=40027
Manual Alarm output passive
Manual Alarm output active