Instructions

15
Device Type : Temperature Controller
Housing&Mounting : 76mm x 34.5mm x 71mm plastic housing for panel
Mounting. Panel cut-out is 71x29mm.
Protection Class : NEMA 4X (Ip65 at front, Ip20 at rear).
Weight : Approximately 0.20 Kg.
Environmental Ratings : Standard, indoor at an altitude of less than 2000 meters
with none condensing humidity.
o o o o
Storage / Operating Temperature : -40 C to +80 C / -30 C to +80 C
Storage / Operating Humidity : 90 % max. (None condensing)
Installation : Fixed installation
Overvoltage Category : II.
Pollution Degree : II, office or workplace, none conductive pollution
Operating Conditions : Continuous
Supply Voltage and Power :
: 115
: 24
: 24
:10 - 30
Temperature Sensor Input : NTC, PTC, TC, RTD
NTC input type : NTC (10 kW @25 °C )
PTC input type : PTC (1000 W @25 °C )
Thermocouple input type : J, K (IEC584.1) (ITS 90)
Thermoresistance input type : PT-100, PT-1000 (IEC751) (ITS 90)
Accuracy : ± 1 % of full scale for thermoresistance
Sensor Break Protection : Upscale
Sampling Cycle : 3 samples per second
Control Form : ON / OFF
Relay Outputs : 16(8) A@250 V V for Resistive load (Compressor output)
(Electrical life : 100.000 switching at full load)
: for Resistive load 5 A@250 V V (Alarm output)
Display : 14 mm Red 4 digits LED Display
o o
LED : S (Green), P (Green), A(Green), C (Yellow), F(Yellow),
Compressor Output (Red),Alarm Output (Red)
Internal Buzzer : ³83dB
Approvals : ,
230V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
V ( %15) 50/60Hz - 1.5VA
VZ 1.5W
V ±
V ±
V ±
W ±
7. Specifications
V Ş Vac,
Z Ş Vdc
Ş Vdc or Vac
can be applied
W
c
8.Optional Accessories
RS-485 Communication Interface
1.RS-485 Module 2.PROKEY Programming Module
The device is programmed(Upload or
Download) by using the parameters.