Instructions
ENGLISH
Defrost at Power On Selection and Defrost Delay Parameter
It can be adjust from 0 to 99 minutes. When tihs parameter is 0, if decrement button is
pressed, is observed. In this condition system goes through a defrost cycle at the
end of the defrost repeat cycle time after power on.If this parameter value is between
0 and 99, then system goes through a defrost cycle at the end of the this parameter time
after power on.
( Default = ) MODBUS ADDRESS:40014
Compressor Start Delay at Power On Parameter ( Default = 0 )
MODBUS ADDRESS:40019
When power is first applied to the device,This time delay must be expired for activation of
compressor. It can be adjusted from 0 to 20 minutes.
Minimum Compressor OFF Time Parameter ( Default = 0 )MODBUS ADDREDS:40021
When compressor is inactive, this time delay must be expired for activation of the
compressor. It can be adjusted from 0 to 20 minutes.
Cabinet Probe Defect Parameter ( Default = 0 ) MODBUS ADDRESS:40023
Compressor Active Time in Case of Cabinet Probe Defect Parameter (Default = 0)
MODBUS ADDRESS:40024
If cabinet probe defect parameter is 2, then this parameter is observed.
It canbe adjusted from to 99 minutes.
Compressor is OFF in case of cabinet probe defect.
Compressor is ON in case of cabinet probe defect.
Compressor operates periodically according to and time periods
in case of cabinet probe defect.
Compressor Start-Start Delay Parameter ( Default = 0 )
MODBUS ADDRESS:40020
This time delay must be expired between two activation of the compressor.
It can be adjusted from 0 to 20 minutes.
Display Status During Defrost Parameter ( Default = 3 )
MODDBUS ADRESS:40015
The cabinet temperature value is displayed during defrost.
Cabinet temperature value at the start of the defrost is displayed during defrost.
Temperature set value is displayed during defrost.
is displayed to indicate the defrost is in progress.
Dripping Time Parameter
This parameter defines for dripping time after defrost.
It
(Default = 2) MODBUS ADDRESS:40017
can be adjusted from 0 to 15 minutes.
Temperature Alarm Delay After Dripping Parameter (Default = 0) MODBUS
ADDRESS:40018
This parameter defines the delay for temperature alarm being active after dripping time
completion. It can be adjusted from 0 to 15 minutes.
Minimum Compressor ON Time Parameter ( Default = 0 )MODBUS ADRES:40022
When compressor is active, this time delay must be expired for deactivation of the
compressor. It can be adjusted from 0 to 20 minutes.
Displaying Current Temperature Delay After Defrost Parameter
This parameter defines the delay for displaying current temperature being active after
defrost.
( Default = 0 )
MODDBUS ADRESS:40016
It can be adjusted from 0 to 255 minutes.
Defrost Stopping Temperature Parameter (Default = 2°C) MODBUS ADDRESS:40013
For evaporator sensor selection parameter is 1 (evaporator sensor is active),
while defrost operation, if evaporator temperature reaches to temperature that defined at
this parameter in a shorter time than parameter, then defrost operation stops.
10
Compressor İnactive Time in Case of Cabinet Probe Defect Parameter
( Default = 0 ) MODBUS ADDRESS:40025
If cabinet probe defect parameter is 2, then this parameter is observed.
It canbe adjusted from to 99 minutes.