Internal Buzzer Heating Controller ESM-3711-H 77x35 DIN Size ESM-3711-H 77 x 35 DIN Size Digital, ON / OFF Temperature Controller - 3 Digits display - PTC Input or, J type Thermocouple Input or, K type Thermocouple Input or, 2-Wire PT 100 Input or, 2-Wire PT 1000 Input (It must be determined in order) - ON/OFF temperature control - Adjustable temperature offset - Set value low limit and set value high limit boundaries - Relay or SSR driver output - Digital Input (Cooking time start/stop input) - Adjustabl
ABOUT INSTRUCTION MANUAL Instruction manual of ESM-3711-H Temperature Controller consists of two main sections. Explanation of these sections are below. Also, there are other sections which include order information and technical specifications of the device. All titles and page numbers in instruction manual are in “CONTENTS” section. User can reach to any title with section number.
Contents 1.PREFACE............................................................................................................................................ Page 1.1 GENERAL SPECIFICATIONS 1.2 ORDERING INFORMATION 1.3 WARRANTY 1.4 MAINTENANCE 5 2.INSTALLATION.................................................................................................................................... Page 2.1 GENERAL DESCRIPTION 2.2 FRONT VIEW AND DIMENSIONS OF ESM-3711-H TEMPERATURE CONTROLLER 2.3 PANEL CUT-OUT 2.
EU DECLARATION OF CONFORMITY Manufacturer Company Name : Emko Elektronik A.S. Manufacturer Company Address: DOSAB, Karanfil Sokak, No:6, 16369 Bursa, Turkiye The manufacturer hereby declares that the product conforms to the following standards and conditions.
1.Preface ESM-3711-H series heating controllers are designed for measuring and controlling temperature. They can be used in many applications with their easy use, On/ Off control form and cooking time properties. Some application fields which they are used are below: Application Fields Glass Food Plastic Petro-Chemistry Textile, Automative Machine Production Industries etc... Applications Heating Baking Ovens Incubators Storages Air Conditioning Etc... 1.
1.2 Ordering Information A BC D E / FG HI / U V W Z / 00 00 / 1 0 0 ESM-3711-H (77x35 DIN Size) 0 A 2 3 4 5 6 9 BC 05 10 11 09 12 15 14 13 Supply Voltage 24V W ( -15%,+10% ) 50/60Hz 24V V ( ± 15% ) 50/60Hz 115V V ( ± 15% ) 50/60Hz 230V V ( ± 15% ) 50/60Hz 12V W ( ± 15% ) 50/60Hz Customer Input Type J, Fe CuNi IEC584.1(ITS90) K, NiCr Ni IEC584.
2.Installation c Before beginning installation of this product, please read the instruction manual and warnings below carefully. In package , - One piece unit - Two pieces mounting clamps - One piece instruction manual A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
2.1 General Description Mounting Clamp Front Panel IP65 protection NEMA 4X Panel surface (maximum thickness 15 mm / 0.59 inch) ESM - 3711-H SV PR SET °C Heating Controller 35 mm / 1.38 inch 2.2 Front View and Dimensions of ESM-3711-H Temperature Controller 77 mm / 3.
Maximum 15 mm / 0.59 inch 58.5 mm / 2.30 inch 4 mm /0.16 inch 2.3 Panel Cut-Out 29 mm / 1.14 inch 50 mm / 1.97 inch (min) 110 mm / 4.33 inch (min) 71 mm / 2.
2.4 Environmental Ratings Operating Conditions Operating Temperature : 0 to 50 °C Max. Operating Humidity : 90% Rh (non-condensing) Altitude c : Up to 2000 m. Forbidden Conditions: Corrosive atmosphere Explosive atmosphere Home applications (The unit is only for industrial applications) 2.5 Panel Mounting 1 1-Before mounting the device in your panel, make sure that the cut-out is of the right size. 2-Insert the device through the cut-out.
2.6 Installation Fixing Clamp 1 The unit is designed for panel mounting. 1-Insert the unit in the panel cut-out from the front side. 2- Insert the mounting clamps to the fixing sockets that located left and right sides of device and make the unit completely immobile within the panel 2 c Montage of the unit to a system must be done with it’s own fixing clamps. Do not do the montage of the device with inappropriate fixing clamps. Be sure that device will not fall while doing the montage. 2.
3.Electrical Wiring c You must ensure that the device is correctly configured for your application. Incorrect configuration could result in damage to the process being controlled, and/or personal injury. It is your responsibility, as the installer, to ensure that the configuration is correct. Device parameters has factory default values. These parameters must be set according to the system’s needs. c c c Only qualified personnel and technicians should work on this equipment.
3.2 Electrical Wiring Diagram c Electrical wiring of the device must be the same as ‘Electrical Wiring Diagram’ below to prevent damage to the process being controlled and personnel injury.
3.3 View of the Device Label Device Label for J Type ( 0 ; 800 ) scaled, with Thermocouple input , 230V V Supply Voltage Input and Relay Output c a Y CAT II P/N : ESM-3711-H - 5.05.0.1/00.00/1.0.0.0 OUTPUT 230 VV ± 15% 10A@250V V 50/60Hz - 1.5VA NO C 1 L NC 2 3 4 DIGITAL INPUT J Type TC ( 0 to 800°C) Scale N 5 6 7 8 9 10 11 12 Device Label for J Type ( 0 ; 800 ) scaled , with 12V W Supply Voltage Input and Relay Output c a CAT II P/N : ESM-3711-H - 6.05.0.1/00.00/1.0.0.
3.
3.5 Temperature Sensor Input Connection 3.5.1 TC (Thermocouple) Connection Connect the wires with the polarity as shown in the figure left. TC 10 11 12 i Always use compensation wire corresponding to the thermocouple used. If present, the shield must be connected to a proper ground. i Input resistance is greater than 10M W. 3.5.2 PTC Connection PTC RED 10 WHITE 11 12 i Pay attention the cable colours of PTC probe while doing the PTC probe connection.
3.6 Galvanic Isolation Test Values of ESM-3711-H Temperature Controller 2000V V ( For ESM-3711-H-5...... ) 500V V ( For ESM-3711-H-3......
3.7 Output Connections 3.7.1 Relay Output Connection L N Device NC C NO c 3 2 c Max 10A V T Fuse 1 Load Fuses must be selected according to the application. 3.7.2 Output (SSR Driver Output) Connection Device 2 L N Last Control Element (SSR) 1 5VZ Max. 15mA c Fuse Load c Fuses must be selected according to the application.
4. Front Panel Definition and Accessing to the Menus Led indication of Led indication of SET value Programming Mode is changing mode active Led indication of Output is Active ESM - 3711-H Cooking Time Active and Temperature Control Delay Active Led SV PR SET Cooking Button Cooking Time (Timer) Value Cooking ON/OFF Button °C Heating Controller Display Temperature Value, Temperature Set Value and Parameters Note-1 It is used to increase the value and access to the parameter in programming mode.
4.2 Changing and Saving Set Value SET Value Screen Main Operation Screen SV SV PR PR SET SET °C °C When SET button is pressed, SV LED lights on and SET value is shown on the display. SET Value Screen Change the SET value with increment and decrement buttons. Main Operation Screen SV SV PR PR SET SET °C °C Press SET button for saving the SET value SV led lights off and main operation screen is shown. 4.
4.4 Programming Mode Parameter List Hysteresis Parameter for Output ( Default = 0 ) From 0 to 100 °C for TC Type devices, From 0 to 100 °C for PT-100 (-50°C , 400°C) and PT-1000 (-50°C , 400°C) , From 0.0 to 10.0 °C for PT-100 (-19.9°C, 99.9°C) and PT-1000 (-19.9°C, 99.9°C) From 0 to 20 °C for PTC (-50°C, 150°C) , From 0.0 to 10.0 °C PTC (-19.9°C, 99.9°C) In ON/OFF control algorithm, temperature Temperature value is tried to keep equal to set value by opening or closing the last control element.
Cooking Time Starting Conditions Parameter ( Default = 0 ) This parameter can be observed if cooking time (Timer) is ³ 1. Cooking time (Timer) is started with cooking ON/OFF button or when cooking time start/stop input is getting closed condition. Cooking time (Timer) is started when temperature reaches to the process set value after pressing cooking ON/OFF button or when cooking time start/stop input is getting closed condition.
Buzzer is Active During This Time ( Default = ) This parameter can be observed if buzzer function selection is ³ 1. It can be adjusted from 1 to 99 minutes. When this parameter is 1, if decrement button is pressed, is observed. Then buzzer becomes active till buzzer silence button Button Protection Parameter ( Default = 0 ) There is no protection Cooking time(Timer) can not be changed. Cooking ON/OFF operation is not performed.
4.
3- When cooking time parameter ³ 1, if selection of temperature control and starting the cooking time parameter = 2 ( Temperature control and cooking time (Timer) can be started by pressing cooking ON/OFF button or when cooking time start/stop input is getting closed condition) is selected; =0 ( Continuous Operation) = 1 ( Interrupted Operation ) Power Power Time Cooking Button starts Buzzer is time Active Cooking Time Active Led Cooking Button starts time Time =1 °C Process Set Time Cooking Button
4.
4.8 Entering to the Programming Mode, Changing and Saving Parameters Operation Screen SV SV PR PR SET SET °C When SET button is pressed for 5 seconds, “PR” led starts to blink. If programming section entering password is different from 0, programming section entering screen is observed.
Programming Screen SV SV PR PR SET SET °C °C Minimum Set Value Parameter Minimum Set Value Press increment button for accessing to the parameter value. Press Set button for accessing to the next parameter. Change the value with increment and decrement buttons. Programming Screen SV SV PR PR SET SET °C Minimum Set Value Press Set button for saving the parameter. i i °C Minimum Set Value Parameter Press Set button for accessing to the next parameter.
5. Failure Messages in ESM-3711-H Heating Controller ESM - 3711-H SV PR SET °C 1- Probe failure in analog inputs. Sensor connection is wrong or there is no sensor connection. When this message is on the screen, if buzzer function selection parameter is 3 or 4 , internal buzzer starts to operate.
6. Specifications Device Type Housing&Mounting : Heating Controler : 77mm x 35mm x 62.5mm plastic housing for panel Mounting. Panel cut-out is 71x29mm. : NEMA 4X (IP65 at front, IP20 at rear). Protection Class : Approximately 0.20 Kg. Weight : Standard, indoor at an altitude of less than 2000 meters Environmental Ratings with none condensing humidity. o o o o Storage / Operating Temperature: -40 C to +85 C / 0 C to +50 C : 90 % max.