User manual
2.2PanelCut-Out
2.GeneralDescription
2.1FrontViewandDimensionsofESM-3711HNTemperatureController
MountingClamp
PanelSurface
(maximumthickness15mm/0.59inch)
FrontPanel
IP65protection
ESM-3711HN77x35 DINSize HeatingController
InstructionManual.ENGESM-3711HN01V0011/14
-4DigitsDisplay
-NTCInputor
PTCInputor
(Mustbedeterminedinorder.)
- Adjustabletemperatureoffset
-Temperaturecontrolwithmanualheatingfunction
- Alarmparameters
- Adjustableinternalbuzzeraccordingtocookingtime,sensor
defectand Alarmstatus.
-Passwordprotectionforprogrammingsection
-InstallingparametersusingProkey
-Remoteaccess,datacollectingandcontrollingwithModbusRTU
-HavingCEmarkaccordingtoEuropeanNorms
-
JTypethermocoupleInputor,
KTypethermocoupleInputor,
2-WirePT-100Inputor,
2-WirePT-1000Input
ON/OFFtemperaturecontrol
- Adjustabletemperatureoffset
-RelayorSSRdriveroutput
-DigitalInput(CookingTimeStart/StopInput)
- Adjustablecookingtimefromfrontpanel
-Temperaturecontrolaccordingtothecookingtime(Timer)
-Usercanselecttostartcookingtime(Timer)whentemperature
reachestothesetvalue
-Buttonprotection
-Setvaluelowlimitandsetvaluehighlimitboundaries
ESM- 77x35DINSize3711HN
Digital,ON/OFFTemperature
Controller
OperatingTemperature:
Max.OperatingHumidity :
Altitude :
0to50°C
90%Rh(non-condensing)
Upto2000m.
Forbidden Conditions:
Corrosive atmosphere
Explosive atmosphere
Home applications (The unit is only for industrial applications)
c
1.2GeneralSpecifications
1.Preface
ESM-3711HN series heating controllers are designed for measuring and controlling
temperature. They can be used in many applications with their easy use, On/ Off control form
and cooking time properties. Some application fields which they are used are below:
ApplicationFields Applications
Glass Heating
Food BakingOvens
Plastic Incubators
Petro-Chemistry Storages
Textile, Automative AirConditioning
MachineProductionIndustriesEtc... Etc...
2
1.1EnvironmentalRatings
3 41615
13 14
A visual inspection of this product for possible damage occurred during shipment is
recommended before installation. It is your responsibility to ensure that qualified mechanical
and electrical technicians install this product.
If there is danger of serious accident resulting from a failure or defect in this unit, power off the
system and separate the electrical connection of the device from the system.
The unit is normally supplied without a power supply switch or a fuse. Use power switch and fuse
as required.
Be sure to use the rated power supply voltage to protect the unit against damage and to prevent
failure.
Keep the power off until all of the wiring is completed so that electric shock and trouble with the
unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering with the unit may results in
malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous atmospheres.
During putting equipment in hole on the metal panel while mechanical installation some metal
burrs can cause injury on hands, you must be careful.
Montage of the product on a system must be done with it’s fixing clamps. Do not do the montage
of the device with inappropriate fixing clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not specified in this instruction
manual.
EMKO Elektronik warrants that the equipment delivered is free from defects in material and
workmanship. This warranty is provided for a period of two years. The warranty period starts
from the delivery date. This warranty is in force if duty and responsibilities which are determined
in warranty document and instruction manual performs by the customer completely.
Repairs should only be performed by trained and specialized personnel. Cut power to the
device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene etc.). Use of
these solvents can reduce the mechanical reliability of the device. Use a cloth dampened in
ethyl alcohol or water to clean the external plastic case.
1.3Installation
1.4Warranty
1.5Maintenance
1.6ManufacturerCompany
ManufacturerInformation:
Repairandmaintenanceserviceinformation:
EmkoElektronikSanayive Ticaret A.Þ.
DemirtaþOrganizeSanayiBölgesiKaranfilSk.No:616369BURSA/TURKEY
Phone:+902242611900
Fax:+902242611912
EmkoElektronikSanayive Ticaret A.Þ.
DemirtaþOrganizeSanayiBölgesiKaranfilSk.No:616369BURSA /TURKEY
Phone:+902242611900
Fax:+902242611912
DeviceType
Housing&Mounting
ProtectionClass
Weight
EnvironmentalRatings
Storage/OperatingTemperature
Storage/OperatingHumidity
Installation
OvervoltageCategory
PollutionDegree
OperatingConditions
SupplyVoltageandPower
TemperatureSensorInput
NTCinputtype
PTCinputtype
Thermocoupleinputtype
Thermoresistanceinputtype
Accuracy
ColdJunctionCompensation
SensorBreakProtection
SamplingCycle
ControlForm
RelayOutputs
OptionalSSRDriveOutput
Display
LED
InternalBuzzer
:HeatingController
:76mmx34.5mmx71mmplastichousingforpanel
Mounting.Panelcut-outis71x29mm.
:Ip65atfront,Ip20atrear.
: Approximately0.20Kg.
:Standard,indooratanaltitudeoflessthan2000meters
withnonecondensinghumidity.
:-40 Cto+80 C/-30 Cto+80 C
:90%max.(Nonecondensing)
:Fixedinstallation
:II.
:II,officeorworkplace,noneconductivepollution
:Continuous
:
:115
:24
:24
:10-30
:NTC,PTC, TC,RTD
:NTC(10k @25°C)
:PTC(1000 @25°C)
:J,K(IEC584.1)(ITS90)
:PT-100,PT-1000(IEC751)(ITS90)
:±1%offullscaleforthermoresistance
: Automatically±0.1°C/±1°C
:Upscale
:3samplespersecond
:ON/OFF
: A@250V forResistiveload(Compressoroutput)
(Electricallife:100.000switchingatfullload)
:Maximum20mA,Maximum17V
:14mmRed4digitsLEDDisplay
:S(Green),P (Green), C(Yellow), F(Yellow),
CompressorOutput(Red),HeatingOutput(Red)
: 83dB
:,
o o o o
o o
W
W
³
16(8) V
Approvals
230V ( %15)50/60Hz-1.5VA
V ( %15)50/60Hz-1.5VA
V ( %15)50/60Hz-1.5VA
V ( %15)50/60Hz-1.5VA
V 1.5WZ
Z
V
V
V
W
±
±
±
±
8.Specifications
All order information of ESM-3711HN Heating Controller are given on the table at above. User may
form appropriate device configuration from information and codes that at the table and convert it to the
ordering codes. Firstly, supply voltage then other specifications must be determined. Please fill the order
code blanks according to your needs. Please contact us, if your needs are out of the standards.
V
Z
Vac,
Vdc
Vdc or Vac
can be applied
Þ
Þ
ÞW
c
11.OrderingInformation
Note-1:If input type is selected PTC or NTC (BC= 12, 18), Temperature sensor is given with the
device.For this reason, if input type is selected as PTC,sensor type (V = 0,1 or 2) or if input type is
selected as NTC, sensor type (V = 0,3 or 4) must be declared in ordering information.
ESM-3711HN
PowerSupply
Input
TemperatureSensor
Input
76mm/3inch
6mm/0.24inch
34,5mm/1.36inch
65mm/2.56inch
Maximum15mm/0.59inch
110mm/4.33inch(min)
71mm/2.79inch
29mm/1.14inch
50mm/1.97inch(min)
230V ( %15)50/60HzV ±
OptionalSupplyVoltage
-30V Z
115V ( %15)50/60Hz,
24V ( %15)50/60Hz,
24V ( %15)50/60Hz,
10
±
±
±
V
V
W
Standard
A BC D E FG HI /
/
U
V W Z/
/
0 1 0 0
1
RelayOutput(16(8) A@250V ,atresistiveLoad,1NO)V
Output-1
E
SupplyVoltageA
InputType
BC
Scale(°C)
ESM-3711HN
4
-50°C/-58°F; 150°C/302°F
12
PTC(Not-1)
Temp.Sensorwhichisgivenwith ESM-3711HN
V
0
None
3
NTC-M5L20.K1.5(NTCSensor,thermoplasticmouldedwith1.5mcable
forcoolingapplication)
4
NTC-M6L50.K1.5(NTCSensor,stainlesssteelhousingwith1.5mcable
forcoolingapplication)
9
Customer
115V ( %15)50/60Hz-1.5VAV ±
5
230V ( %15)50/60Hz-1.5VAV ±
00 00
8
10-30V Z
-50°C/-58°F; 100°C/212°F
18
NTC(Not-1)
1
PTC-M6L40.K1.5(PTC AirProbe1.5mtSiliconCable)
2
PTCS-M6L30.K1.5.1/8”(PTCLiquidProbe1.5mtSiliconCable)
(77x35DINSizes)
10.Optional Accessories
RS-485CommunicationInterface
1.RS-485Module 2.PROKEY ProgrammingModule
Thedeviceisprogrammed(Uploador
Download)byusingtheparameters.
0°C/32°F; 800°C/1472°F
05
J,FeCuNiIEC584.1(ITS90)
0°C/32°F; 999°C/1830°F
10
K,NiCrNiIEC584.1(ITS90)
-50°C/-58°F; 400°C/752°F
11
PT 100,IEC751(ITS90)
-19.9°C/-4°F; 99.9°C/212°F
09
PT 100,IEC751(ITS90
-50°C/-58°F; 400°C/752°F
14
PT 1000,IEC751(ITS90)
-19.9°C/-4°F; 99.9°C/212°F
13
PT 1000,IEC751(ITS90
3
24V ( %15)50/60Hz-1.5VAV ±
NTC,PTC,
JorKTypeTC
2-WirePT-100
PT-10002-Wire
Output-1
ControlOutput
AlarmOutput
Output-1
Standard
Optional
(RelayOutput)
(SSRDriveOutput)
HeatingFunction
ON/OFFOperation
ControlOutput
AlarmOutput
2
SSRDriver Maximum20m,Maximum17VOutput( )Z
2
24V ( %15)50/60Hz-1.5VAW ±
DigitalInput
CookingTime(Timer)
Start/StopInput
WhenSET buttonispressedfor5
seconds,“P”ledstartstoblink.If
programmingmodeentering
passwordisdifferentfrom0,
programmingmodeenteringscreen
willbeobserved.
MainOperationScreen
ProgrammingScreen
Changethevaluewithincrement
anddecrementbuttons.
TemperatureUnitSelection
ParameterValue
Press SET button for accessing to the parameter
value. Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter.
PressOKbuttonforsavingthe
parameter.
Press increment button for accessing to the
next parameter, press decrement button for
accessing to the previous parameter
PasswordEnteringScreen
ProgrammingMode
EnteringScreen
PressOKbuttonfor
accessingtothe
passwordentering
screen.
PasswordEnteringScreen
Enterprogrammingmodeaccessingpassword
withincrementanddecrementbuttons.
Note2: If programming mode accessing password is 0, only three parameters are accessible, and the
parameter values can be changed.
PressOKbuttonforentering
thepassword.
Note1: Ifprogramming
modeaccessing
passwordis0,
TemperatureUnitscreen
isobservedinsteadof
programmingscreen
TemperatureUnitSelection
ParameterValue
If no operation is performed in programming mode for 20 seconds, device turns to main
operation screen automatically..
i
DecimalSeperator
EnablingParameter
6.6EnteringToTheProgrammingMode,ChangingandSavingParameter
6.5OperationGraphicsofESM3711HNHeatingController
3- When cooking time parameter 1, if selection of temperature control and starting the
cooking time parameter = 2 ( Temperature control and cooking time (Timer) can be started
by pressing cooking ON/OFF button or when
is selected;
³
cooking time start/stop input is getting closed
condition)
Hst
°C
Buzzeris
Active
Cooking
Buttonstarts
time
Hst
°C
(ContinuousOperation)
=
(Interrupted )Operation
=
0
1
=1
4-ManualControl:Ifcookingtime(Timer)
=
Hst
°C
TemperatureControl
is Active
Power
Time
Hst
Process
Set
Process
Output
°C
Temperature
Control
is Active
=
Cooking
Buttonstarts
thetemperature
control
=
0or1
=
2
Cooking
Time
Active
Led
(TemperaturecontrolstartswithcookingON/OFFbuttonor
when )cookingtimestart/stopinputisgettingclosedcondition
(Temperaturecontrolstartsatpoweron)
Time
Time
Time
Time
Time
Time
Time
Process
Output
Process
Set
Cooking
Time
Active
Led
Power
Cooking
Buttonstarts
thetemperature
control
Cooking
Buttonstops
thetemperature
control
Cooking
Buttonstops
thetemperature
control
Temperature
Control
is Active
Power
Power
Cooking
Time
Active
Led
Cooking
Time
Active
Led
Process
Set
Process
Set
Temperature
Control
is Active
Temperature
Control
is Active
Process
Output
Process
Output
Time
Time
Time
Time
TemperatureControl
is Active
Cooking
Buttonstarts
time
Cooking
Buttonstarts
time
Cooking
Buttonstarts
time
Time
Time
Time
Time
Buzzeris
Active
=1
YourTechnologyPartner
www.emkoelektronik.com.tr
Thankyouverymuchforyourpreferenceto
useEmkoElektronikproducts,pleasevisitour
webpagetodownloaddetailedusermanual.
7.CookingTime(Timer)ON/OFFOperation
ü
3sec.
In main operation screen, If cooking button is pressed for
3 seconds, then cooking time (Timer) is started and
cooking time active led becomes active. While cooking
time (Timer) continues if cooking button is pressed for 3
seconds, cooking time (Timer) is finished and cooking
time active led lights off.
If button protection parameter = 4 cooking time
(Timer) ON/OFF operation is performed when
button is pressed.
7.1CookingTime(Timer)ON/OFFOperationwithCookingTimeStart/StopInput
When K switch that is connected to the cooking time
start/stop input, getting closed condition, cooking time
(Timer) is started and cooking time active led becomes
active. While cooking time (Timer) continues if K switch
getting open condition, cooking time (Timer) is finished
and cooking time active led lights off.
DIGITAL INPUT
K
6
7
ü
O
F
O
C
S
P
ü
O
F
O
C
S P
ü
O
F
O
C
S P
ü
O
F
O
C
S P
ü
ü
O
F
O
C
S P
ü
O
F
O
C
S P
1- Screen Blinking
Sensor failure . Sensor connection is wrong or there is no sensor connection. If buzzer function
selection parameter is 3 or 4, internal buzzer starts to operate.
9.FailureMessagesinESM-3711HNHeatingController
Example:Ifalarmfunctionselectionparameterinprogrammingsectionis1(Absolute Alarm)
andmaximumalarmparameteris50Whentemperatureisabove50°C,valueonthescreen
startstoblink. Alsobuzzerfunctionselectionparameteris2or4,theninternalbuzzerison.
2- Main Screen Value is Blinking.
ü
ü
ü
O
F
O
C
S P
O
F
O
C
S P
O
F
O
C
S P
O
F
O
C
S P