Instructions

ENGLISH
ON/OFF Parameter ( Default = 0 ) MODBUS ADDRESS:40030
When device energized; if (increment button) pressed for 10 seconds, device stops
controlling and screen will be displayed. If (increment button) pressed again for
10 seconds, device continues controlling and display changes back to main operating
screen.
ON/OFF function with button is not available.
ON/OFF function with button is available.
11
Temperature Alarm On Delay Time Parameter(Default = 0)MODBUS ADDRESS:40023
Temperature alarm on delay time can be defined with this parameter.
It can be adjusted from 0 to 99 minutes.
Temperature Alarm Delay After Power On Parameter
When power is first applied to the device, this time delay must be expired for activation of
temperature alarm. It can be adjusted from 0 to 99 minutes.
( Default = 0 )
MODBUS ADRES:40024
Buzzer Function Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40025
Buzzer is inactive.
Buzzer is active during defrost operation.
Buzzer is active if an alarm occurs.
Buzzer is active during sensor failures.
Buzzer is active during defrost operation, alarm or sensor failures.
Button Protection Parameter ( Default = 4 ) MODBUS ADDRESS:40027
There is no protection.
Defrost time can not be changed and manual defrost is not available.
Temperature Set value can not be changed.
Defrost time set value and temperature set value can not be changed. Manual
defrost is not available.
Buzzer is active during this time
When this parameter is 1, if decrement button is pressed, is observed. In this
condition buzzer is active till buzzer silence button is pressed.
( Default = ) MODBUS ADDRESS:40026
If buzzer function selection parameter value =0, this parameter can not be
observed. Buzzer stays active during this time. It can be adjusted from 1 to 99 minutes
Programming Section Accessing Password
. If password selected ‘12’, only , and
parameters will be accessible.
( Default = 0 ) MODBUS ADDRESS:40031
It is used for accessing to the programming section. It can be adjusted from 0 to 999. If it is
selected 0, password will not be asked
Defrost time value can not be changed, manual defrost is available..
PROKEY communication selected.
Communication Mode Selection Parameter ( Default = 0 ) MODBUS ADDRESS:40028
Rs485 communication selected.
Slave ID Parameter ( Default = 1 ) MODBUS ADDRESS=40029
Device communication address parameter (1 to 247).