4.2.5 Adjustment of Set Offset Value
Set offset value can be adjusted with set offset trimpot that is located on front panel.
When temperature is not equal to SET value, to remove the difference between SET value and
temperature and to make equal the temperature and SET value, Set offset is used. It can be
adjusted from -20% to 20% of full scale.
Minimum and maximum value of Set offset value according to the type and scale of the device are
given below:
SV-OFFSET
+
-
0
For PT-100 ( -100.0 to 100.0 )°C scaled devices : (-20.0 to +20.0)°C
For PT-100 ( 0.0 to 200.0 )°C scaled devices : (-20.0 to +20.0)°C
For PT-100 ( 0 to 400 )°C scaled devices : (-8 to 8)°C
For J Type TC ( 0 to 400 )°C scaled devices : (-8 to 8)°C
For J Type TC ( 0 to 800 )°C scaled devices : (-16 to 16)°C
For K Type TC ( 0 to1200 )°C scaled devices : (-24 to 24)°C
For R Type TC ( 0 to 1600 )°C scaled devices : (-32 to 32)°C
For S Type TC ( 0 to 1600 )°C scaled devices : (-32 to 32)°C
Set offset Values according to the type and scale of the device
Temperature
Control Output (%)
100
0
Proportional Band = Scale * (%PB)
Temperature
SET-Proportional Band
SET-OFFSET SET+OFFSET
SET