User manual

22
0.25% of full scale is
selected
1
2
1
2
1
1
2
2
Hysteresis Value Selection
0.5% of full scale is
selected
1% of full scale is
selected
2% of full scale is
selected
Minimum and maximum value of hysteresis according to the type and scale of the device are
given below:
For PT-100 ( -100.0 to 100.0 )°C: ( 0.0 to 0.5 )°C
For PT-100 ( 0.0 to 200.0 )°C : (0.0 to 0.5)°C
For PT-100 ( 0 to 400 )°C : (0 to 1)°C
For J Type TC ( 0 to 400 )°C : (0 to 1)°C
For J Type TC ( 0 to 800 )°C : (0 to 2)°C
For K Type TC ( 0 to 1200 )°C : (0 to 3)°C
For R Type TC ( 0 to 1600 )°C : (0 to 4)°C
For S Type TC ( 0 to 1600 )°C : (0 to 4)°C
If 0.25% of full scale is selected with DIP
Switch, then hysteresis;
For PT-100 ( -100.0 to 100.0 )°C : ( 0.0 to 1.0 )°C
For PT-100 ( 0.0 to 200.0 )°C : (0.0 to 1.0)°C
For PT-100 ( 0 to 400 )°C : (0 to 2)°C
For J Type TC ( 0 to 400 )°C : (0 to 2)°C
For J Type TC ( 0 to 800 )°C : (0 to 4)°C
For K Type TC ( 0 to 1200 )°C : (0 to 6)°C
For R Type TC ( 0 to 1600 )°C : (0 to 8)°C
For S Type TC ( 0 to 1600 )°C : (0 to 8)°C
If 0.5% of full scale is selected with DIP
Switch, then hysteresis;
For PT-100 ( -100.0 to 100.0 )°C : ( 0.0 to 2.0 )°C
For PT-100 ( 0.0 to 200.0 )°C : (0.0 to 2.0)°C
For PT-100 ( 0 to 400 )°C : (0 to 4)°C
For J Type TC ( 0 to 400 )°C : (0 to 4)°C
For J Type TC ( 0 to 800 )°C : (0 to 8)°C
For K Type TC ( 0 to 1200 )°C : (0 to 12)°C
For R Type TC ( 0 to 1600 )°C : (0 to 16)°C
For S Type TC ( 0 to 1600 )°C : (0 to 16)°C
If 1% of full scale is selected with DIP
Switch, then hysteresis;
For PT-100 ( -100.0 to 100.0 )°C : ( 0.0 to 4.0 )°C
For PT-100 ( 0.0 to 200.0 )°C : (0.0 to 4.0)°C
For PT-100 ( 0 to 400 )°C : (0 to 8)°C
For J Type TC ( 0 to 400 )°C : (0 to 8)°C
For J Type TC ( 0 to 800 )°C : (0 to 16)°C
For K Type TC ( 0 to 1200 )°C : (0 to 24)°C
For R Type TC ( 0 to 1600 )°C : (0 to 32)°C
For S Type TC ( 0 to 1600 )°C : (0 to 32)°C
If 2% of full scale is selected with DIP
Switch, then hysteresis;
ONOFF
ONOFF
ON
ON
OFF
OFF