Set value can be adjusted with Set Value Adjustment Potentiometer that is on the front panel. Set
value range changes according to the type and scale of the device. Minimum and maximum
values of Set value according to the device type are given below:
4.2.1 Set Values
4.2 Operation Settings
4.2.2 ON/OFF , Time Proportional Operation Form Selection
15
30
PB%
0
ON
OFF
Operation form can be adjusted with proportional band adjustment and ON/OFF Control Form
selection trimpot that is on the front panel.
Trimpot is adjusted to point out ON/OFF part for ON/OFF Control
form.
15
30
PB%
0
ON
OFF
Trimpot is adjusted to point out different from ON/OFF part for
proportional operation. Proportional Band Value can be adjusted
from 0% to 30% of full scale.
Minimum and maximum value of proportional band according to the
type and scale of the device are given below:
For PT-100 ( -100.0 to 100.0 )°C
For PT-100 ( 0.0 to 200.0 )°C
For PT-100 ( 0 to 400 )°C
For J Type TC ( 0 to 400 )°C
For J Type TC ( 0 to 800 )°C
For K Type TC ( 0 to 1200 )°C
For R Type TC ( 0 to 1600 )°C
For S Type TC ( 0 to 1600 )°C
Set Values according to the Type and Scale of the Device
Proportional Band Values according to the type and scale
of the device
For PT-100 ( -100.0 to 100.0 )°C scaled device: 0.0 to 60.0°C
For PT-100 ( 0.0 to 200.0 )°C scaled device : 0.0 to 60.0°C
For PT-100 ( 0 to 400 )°C scaled device : 0 to 120°C
For J Type TC ( 0 to 400 )°C scaled device : 0 to 120°C
For J Type TC ( 0 to 800 )°C scaled device : 0 to 240°C
For K Type TC ( 0 to1200 )°C scaled device : 0 to 360°C
For R Type TC ( 0 to 1600 )°C scaled device : 0 to 480°C
For S Type TC ( 0 to 1600 )°C scaled device : 0 to 480°C