: Alarm-1 set value. (Default: 300) Modbus Address: 40036
: Alarm-1 hysteresis value. It can be adjusted from %0 to %50 of the scale
( - ). (Default: 0) Modbus Address: 40037
: Alarm-1 type selection. (Default: ) Modbus Address: 40038
: Alarm-1 set low limit parameter. It can be adjusted from operation scale minimum
to alarm-1 set high limit. (Default: 0) Modbus Address: 40039
: Alarm-1 set high limit parameter. It can be adjusted from alarm-1 set low limit to
operation scale minimum. (Default: 500) Modbus Address: 40040
: Alarm-1 on Delay Time. It can be adjusted from 0 to 9999 seconds. (Default: 0)
Modbus Address: 40041
: Alarm-1 off Delay Time. It can be adjusted from 0 to 9998 seconds. If it is higher
than 9998, is seen on the screen and alarm latching output is selected. In alarm
latching output mode in order to m ake passive alarm outputs, press enter button at
main screen. (Default: 0) Modbus Address: 40042
PID menu parameters can be seen only if parameter is .
: If tune param eter is set to , device start to calculate PID parameters
automatically. (Default: ) Modbus Address: 40027
: Proportional band. It can be adjusted from %1.0 to %100.0. (Default: 10.0)
Modbus Address: 40028
: Integral Time. It can be adjusted from 0 to 3600 second. (Default: 100) Modbus
Address: 40029
: Derivative Time. It can be adjusted from 0.0 to 999.9 second. (Default: 25.0)
Modbus Address: 40030
: Output Control Per iod. It can be adjusted from 0.5 to 150 second. (Default: 10.0)
Modbus Address: 40031
: Set value offset. (Set + ) is used as set value in PID calculations. This
parameter is used for shifting the propo rtional band. It can be adjusted from (- /2) to
( /2). (Default: 0) Modbus Address: 40032
: Control Menu Parameters
: PID Menu Parameters
: Alarm-1 Menu Parameters
: Alarm-2 Menu Parameters (Only for devices with two rela ys)
: Communication Parameters (Only for devices with RS-485 com.)
: Protecion Menu Parameters
Deviation Range
High Alarm
Installation
In package,
-One piece unit
-Two pieces mounting clamp
-One piece instruction manual
A visual inspection of this product for possible damage occured
during shipment is recommended before installation. It is your
responsibility to ensure that qualified mechanical and electrical
technicians install this product.
If there is danger of serious accident resulting from a failure or defect
in this unit, power off the system and the electrical connection of the
device from the system.
The unit is normally supplied without a power switch or a fuse. Use
power switch and fuse as required.
Be sure to use the rated power supply voltage to protect the unit
against damage and to prev ent failure.
Keep the power off until all of the wiring is completed so that electric
shock and trouble with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering
with the unit may results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous
atmospheres. During the equipment is putted in hole on the metal
panel while mechanical installation some metal burrs can cause
injury on hands, you must be careful.
Montage of the produ ct on a system must be done with it’s mounting
clamp. Do not do the montage of the device with inappropriate
mounting clamp. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not
specified in this instruction manual.
Before beginning installation of this product, please
read the instruction manual and warnings below
carefully.
Warranty
EMKO Elektronik warrants that the equipment delivered is free from
defects in material and workmanship. This warranty is prov ided for a
period of two years. The warranty period starts from the delivery
date.
This warranty is in force if duty and responsibilities which are
determined in warranty document and instruction manual performs
by the customer completely.
Maintenance
Repairs should only be performed by trained and specialized
personnel. Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol,
Trichlorethylene etc.). Use of these solvents can reduce the
mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone: +90 224 261 1900
Fax: +90 224 261 1912
a
Repair and Maintenance Service Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone: +90 224 261 1900
Fax : +90 224 261 1912
Before commissioning the device, parameters must be set in
accordance with desired use. Incomplete or incorrect configuration
can cause dangerous stiuations.
Because of limited mechanical life of relay output contact, SSR
output is recommended which the device use PID control algoritm.
The device with ON/OFF control algoritm, hysteresis parameter must
be set a suitable value for your system, to avoid too much relay
switching.
Vac,
Vdc,
Vdc or Vac can be applied
: Process Menu Parameters
: Process input type selection; (Default: ) Modbus Address: 40004
: J type (Fe,Cu,Ni) Thermocouple , -199ºC,900ºC ; -199ºF,999ºF
: K type (Ni,Cr,Ni) Thermocouple , -199ºC,999ºC ; -199ºF,999ºF
: R type (Pt13%RhPt) Thermocouple , 0ºC,999ºC ; 32ºF,999ºF
: S type (Pt10%RhPt) Thermocouple , 0ºC,999ºC ; 32ºF,999ºF
: T type (Cu,Cu,Ni) Thermocouple , -199ºC,400ºC ; -199ºF,752ºF
: Pt-100 , -199ºC ,650ºC ; -199ºF,999ºF
: Unit Selection. or can be chosen. (Default: ) Modbus Address: 40005
: Operation Scale minimum (Low Limit) value. It changes according to the process
input type and scale. (Default: -199) Modbus Address: 40006
: Operation Scale maximum (High Limit) value. It changes according to the
process input type and scale. (Default: 900) Modbus Address: 40007
: Process Set value Low Limit. Minimum set value is defined with this parameter.
It changes according to the process input type and scale.(Default: -199) Modbus
Address: 40008
: Process Set value High Limit. Maximum set value is defined with this parameter.
It changes according to the process input type and scale. (Default: 900) Modbus
Address: 40009
: Display offset for process value. It can be adjusted from -10% of scale to 10% of
scale. It is added to the process display value. (Default: 0) Modbus Address: 40010
: Define filter time(sec) for displayed value. (Default: 1.0) Modbus Address: 40011
: This parameter determines, which output will be Process control output. If is
chosen, process output is relay output, if is chosen, process output is SSR output.
(Default: ) Modbus Address: 40015
: Process Type Selection. It can be (Heating) or (Cooling).(Default: )
Modbus Address: 40016
: Process Control Type Selection. It can be or . (Default: ) Modbus
Address: 40017
: Hysteresis value. It can be adjusted from %0 to %50 of the Scale ( - ).
If = , then this parameter can be seen. (Default: 3) Modbus Address: 40018
: Sensor Break Output Value. It can be adjusted from %0 to %100. (Default: 0.0)
Modbus Address: 40019
: The choice of displayed text on process value display when sensor is broken.
It can be or . (Default: ) Modbus Address: 40020
: Soft Start Set value. Device operates in Soft Start mode, until the temperature
reaches Soft Start set value. If is selected, Soft Start mode is disabled. (Default: )
Modbus Address: 40021
: Soft Start Control Output. This parameter determines soft start mode control
output percentage. It can be adjusted from %10 to %90. (Default: 10.0) Modbus
Address: 40022
: Soft Start Control Time. This parameter determines soft start mode control time.
(Default: 1.0) Modbus Address: 40023
Alarm-2 menu parameters can be seen only if parameter is .
: Alarm-2 set value. (Default: 400) Modbus Address: 40046
: Alarm-2 hysteresis value. It can be adjusted from %0 to %50 of the Scale
( - ). (Default: 0) Modbus Address: 40047
: Alarm-2 type selection. (Default: ) Modbus Address: 40048
: Alarm-2 set low limit parameter. It can be adjusted from operation scale minimum
to alarm-2 set high limit. (Default: 0) Modbus Address: 40049
: Alarm-2 set high limit parameter. It can be adjusted from alarm-2 set low limit to
operation scale maximum. (Default: 500) Modbus Address: 40050
: Alarm-2 on delay time. It can be adjusted from 0 to 9999 seconds. (Default: 0)
Modbus Address: 40051
: Alarm-2 off delay time. It can be adjusted from 0 to 9998 seconds. If it is higher
than 9998, is seen on the screen and Alarm Latching Output is selected. In
alarm latching output mode in order to make passive alarm outputs, press enter
button at main screen. (Default: 0) Modbus Address: 40052
: Communication accessing address of device. (Default: 1) Modbus
Address: 40056
: Communication Baud Rate. (Default: 3) Modbus Address: 40057
: 1200 Baud Rate.
: 2400 Baud Rate.
: 4800 Baud Rate.
: 9600 Baud Rate.
: 19200 Baud Rate.
: 38400 Baud Rate.
: Parity Selection for Communication. (Default: 0) Modbus Address: 40058
: No Parity.
: Odd Parity.
: Even Parity.
: Stop Bit Selectio n for Communication. (Default: 0) Modbus Address: 40059
: 1 Stop Bit.
: 2 Stop Bit.
: Password for accessing to the programming section. It can be adjusted from 0 to
9999. If is 0, password screen is not seen. If is different from 0 and user
enters to the m enu pages without entering the password, all the menus can be
observed except protection menu . But device does not allow to do any changes
in parameters. (Default: 0) Modbus Address: 40063
: User default parameters. This parameter is used for saving all parameters to
restore later or restore all parameters saved before. If is chosen, all parameters
saved before are restored. If is chosen, all parameters saved to restore later. If
is chosen, nothing is changed. (Default: ) Modbus Address: 40064
: This parameter is used for restore factory defaults. If is chosen, factory
defaults parameters restored. If is chosen, nothing is changed. (Default: )
Modbus Address: 40065
Error Messages
Remove all input/output connections on terminals before restoring
parameters to user/factory defaults.
Modbus Addresses of Device Operation Info. (Read Input Register)
Modbus Address: 30000
Modbus Address: 30001
Modbus Address: 30002
Displayed Temperature Value
Status of LEDs: bit.1 ALR1, bit.2 ALR2, bit.9 °C
bit.10 °F, bit.11 PO2, bit.12 PO1
Status of Device: bit.0 Sensor Break Status
Alarm Types
Alarm
Set
Alarm
Hysteresis
Alarm
Hysteresis
Alarm
Set
Process
Set
Process
Set
Alarm
Set
Alarm
Hysteresis
Alarm
Hysteresis
Process
Set
Process
Set
Alarm
Set
Alarm
Output
Alarm
Output
Alarm
Output
Alarm
Output
Process Value
Process Value
Process Value
Process Value
Process High
Alarm
Process Low
Alarm
Deviation High
Alarm
Deviation Low
Alarm
Process
Set
Alarm
Set
Process
Set
Process
Set
Alarm
Set
Alarm
Hysteresis
Alarm
Hysteresis
Alarm
Output
Process Value
Deviation Band
Alarm
Process
Set
Alarm
Set
Process
Set
Alarm
Hysteresis
Process
Set
Alarm
Set
Process
Set
Process
Set
Alarm
Set
Alarm
Hysteresis
Alarm
Hysteresis
Alarm
Output
Alarm
Output
Process Value
Process Value
Deviation Range
Alarm
1-Sensor failure in analog inputs. Sensor connection is wrong or there
is no sensor connection.
a
2-If programming section entering password is different from “0” and
user accesses to the parameter by enter button without entering the
password and wants to change a parameter, the warning message is
shown on the bottom display as shown on the left. Device does not
allow to do any changes without enteri ng the password corre ctly.
a
3-If value that is read from the analog input is lower than process set
low limit parameter value ( ), value on the top display starts to blink
as shown on the picture.
a
4-If value that is read from the analog input is higher than process set
high limit parameter value ( ), value on the top display starts to
blink as shown on the picture.
a
5-If value that is read from the analog input is lower than sensor scale
low limit, value on the top display starts to blink as shown on the
picture.
a
6-If value that is read from the analog input is higher than sensor scale
high limit, value on the top display starts to blink as shown on the
picture.
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
Ordering Information
Eco PID ( 48x48 DIN 1/16 )
Dimension
48x48 DIN 1/16
A
4
A
4 .
B
.
C
.
D
S .
E
Outputs-1
1R
1 x Relay Output (5A@250V at Resistive Load) (NO,C)
C
2R
2 x Relay Output (5A@250V at Resistive Load) (NO,NO,C)
S SSR Driver Output (Max. 10mA, Max. 12V)
Outputs-2
D
Communication
0
None
485
RS-485 Communication
E
Supply VoltageB
10...30V
115V (±%15) 50/60Hz
230V (±%15) 50/60Hz
Customer
3
5
6
9