User manual
1-Sensor failure in analog inputs. Sensor connection is wrong or there
is no sensor connection.
a
2-If programming section entering password is different from “0” and
user accesses to the parameter by enter button without entering the
password and wants to change a parameter, the warning message is
shown on the bottom display as shown on the left. Device does not
allow to do any changes without entering the password correctly.
a
3-If value that is read from the analog input is lower than process set
low limit parameter value ( ), value on the top display starts to blink
as shown on the picture.
a
4-If value that is read from the analog input is higher than process set
high limit parameter value ( ), value on the top display starts to
blink as shown on the picture.
a
5-If value that is read from the analog input is lower than sensor scale
low limit, value on the top display starts to blink as shown on the
picture.
a
6-If value that is read from the analog input is higher than sensor scale
high limit, value on the top display starts to blink as shown on the
picture.
PO2
PO1
AL1
AL2
°C
°F
/
Error Messages
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
PO2
PO1
AL1
AL2
°C
°F
/
Installation
In package,
-One piece unit
-Two pieces mounting clamp
-One piece instruction manual
A visual inspection of this product for possible damage occured
during shipment is recommended before installation. It is your
responsibility to ensure that qualified mechanical and electrical
technicians install this product.
If there is danger of serious accident resulting from a failure or defect
in this unit, power off the system and the electrical connection of the
device from the system.
The unit is norm ally supplied without a power switch or a fuse. Use
power switch and fuse as required.
Be sure to use the rated power supply voltage to protect the unit
against damage and to prevent failure.
Keep the power off until all of the wiring is completed so that electric
shock and trouble with the unit can be prevented.
Never attempt to disassemble, modify or repair this unit. Tampering
with the unit may results in malfunction, electric shock or fire.
Do not use the unit in combustible or explosive gaseous
atmospheres. During the equipment is putted in hole on the metal
panel while mechanical installation some metal burrs can cause
injury on hands, you must be careful.
Montage of the product on a system must be done with it’s mounting
clamp. Do not do the montage of the device with inappropr iate
mounting clam p. Be sure that device will not fall while doing the
montage.
It is your responsibility if this equipment is used in a manner not
specified in this instruction manual.
Before beginning installat ion of this product, please
read the instruction manual and warnings below
carefully.
Warranty
EMKO Elektronik warrants that the equipment delivered is free from
defects in materia l and workmanship. This warranty is provided for a
period of two years. The warranty period starts from the delivery
date.
This warranty is in force if duty and responsibilities which are
determined in warran ty document and instruction manual performs
by the customer completely.
Maintenance
Repairs should only be performed by trained and specialized
personnel. Cut power to the device before accessing internal parts.
Do not clean the case with hydrocarbon-based solvents (Petrol,
Trichlorethylene etc.). Use of these solvents can reduce the
mechanical reliability of the device. Use a cloth dampened in ethyl
alcohol or water to clean the external plastic case.
Other Informations
Manufacturer Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone: +90 224 261 1900
Fax: +90 224 261 1912
a
Repair and Maintenance Service Information:
Emko Elektronik Sanayi ve Ticaret A.Ş.
Demirtaş Organize Sanayi Bölgesi Karanfil Sk. No:6 16369
BURSA/TURKEY
Phone: +90 224 261 1900
Fax : +90 224 261 1912
Before commissioning the device, parameters must be set in
accordance with desired use. Incomplete or incorrect configuration
can cause dangerous stiuations.
Because of limited mechanical life of relay output contact, SSR
output is recommended which the device use PID control algoritm.
The device with ON/OFF control algoritm, hysteresis parameter must
be set a suitable value for your system, to avoid too much relay
switching.
Vac,
Vdc,
Vdc or Vac can be applied
Ordering Information
Eco LITE ( 48x48 DIN 1/16 )
Dimension
48x48 DIN 1/16
A
4
A
4 .
B
.
C
.
D
0 .
E
0
Outputs-1
1R
1 x Relay Output (5A@250V at Resistive Load) (NO,C)
C
2R
2 x Relay Output (5A@250V at Resistive Load) (NO,NO,C)
Supply VoltageB
10...30V
115V (±%15) 50/60Hz
230V (±%15) 50/60Hz
Customer
3
5
6
9