Technical data

3 | ENGLISH
Caution! If you operate devices that do not correspond to the technical specifications
(see technical data), you can damage the connected devices and the radio receiver.
Only connect luminaires to the dimmer.
Do not connect luminaires with energysaving lamp(s).
Do not connect combinations of electronic and conventional transformers
Only dimmable transformers may be connected.
Connecting combinations of transformers and ohmic loads, incandescent lamps,
230 V halogen lamps is only permitted if the power of the ohmic load is max. 30%
of the entire connected load.
Note: Do not use dimmers on socket-outlets! The risk of overloading and the risk of
unsuitable appliances being connected is too high.
Note: If the load on connected wound transformers is too low, the dimmer may
malfunction during operation. The load on the transformer should therefore be at least
40% of the nominal power of the transformer.
Note: An excessive load will trigger the dimmer's overload protection. Reduce the
connected load and then switch the dimmer on again.
Note: If you install several dimmers next to each other, reduce the maximum load
allowed by 20% because of the reduced heat dissipation.
Figure 1 – EM6610 connectors